VACON® 3000
Application Guide
8.2.47.2 Fault Code 68, ID 1302 - Maintenance Counter 1 Fault
Cause
The value of the maintenance counter is higher than the fault limit.
Troubleshooting
Do the necessary maintenance.
Reset the counter. See parameter Maintenance Counter 1 Reset (ID 490).
8.2.48 Fault Code 69 - Fieldbus Mapping Error
8.2.48.1 Fault Code 69, ID 1310 - Fieldbus Mapping Error
Cause
The ID number that is used to map the values to Fieldbus Process Data Out is not valid.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
8.2.48.2 Fault Code 69, ID 1311 - Fieldbus Mapping Error
Cause
It is not possible to convert 1 or more values for Fieldbus Process Data Out.
The type of the value is undefined.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
8.2.48.3 Fault Code 69, ID 1312 - Fieldbus Mapping Error
Cause
There is an overflow when the values for Fieldbus Process Data Out (16-bit) are mapped and converted.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
8.2.49 Fault Code 76 - Start Prevented
8.2.49.1 Fault Code 76, ID 1076 - Start Prevented
Cause
The start command is blocked to prevent the accidental rotation of the motor during the first power-up.
Troubleshooting
Reset the drive to start the correct operation. The parameter settings tell if it is necessary to restart the drive.
8.2.50 Fault Code 77 - >5 Connections
8.2.50.1 Fault Code 77, ID 1077 - > 5 Connections
Cause
There are more than 5 active fieldbus or PC tool connections. You can use only 5 connections at the same time.
Troubleshooting
Leave 5 active connections. Remove the other connections.