8.2.6.7 Fault Code 8, ID 606 - System Fault
Cause
The software of the control unit is not compatible with the software of the power unit.
Troubleshooting
Reset the fault and restart the drive.
Download the latest software from the Danfoss Drives website. Update the drive with it.
If the fault occurs again, ask for instructions from your nearest distributor.
8.2.6.8 Fault Code 8, ID 607 - System Fault
Cause
The software version cannot be read. There is no software in the power unit.
Defective component.
Troubleshooting
Reset the fault and restart the drive.
Download the latest software from the Danfoss Drives website. Update the drive with it.
If the fault occurs again, ask for instructions from your nearest distributor.
8.2.6.9 Fault Code 8, ID 608 - System Fault
Cause
Troubleshooting
Reset the fault and restart the drive.
Download the latest software from the Danfoss Drives website. Update the drive with it.
If the fault occurs again, ask for instructions from your nearest distributor.
8.2.6.10 Fault Code 8, ID 609 - System Fault
Cause
Defective component.
Operation malfunction.
Troubleshooting
Reset the fault and make a power down of the drive twice.
Download the latest software from the Danfoss Drives website. Update the drive with it.
8.2.6.11 Fault Code 8, ID 610 - System Fault
Cause
Defective component.
Operation malfunction.
Troubleshooting
Reset the fault and restart.
Download the latest software from the Danfoss Drives website. Update the drive with it.
If the fault occurs again, ask for instructions from your nearest distributor.