8.2.29.2 Fault Code 44, ID 432 - Device Changed (Different Type)
Cause
•
The option board in slot B was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
•
Reset the fault. Set the option board parameters again.
8.2.29.3 Fault Code 44, ID 433 - Device Changed (Different Type)
Cause
•
The option board in slot C was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
•
Reset the fault. Set the option board parameters again.
8.2.29.4 Fault Code 44, ID 434 - Device Changed (Different Type)
Cause
•
The option board in slot D was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
•
Reset the fault. Set the option board parameters again.
8.2.29.5 Fault Code 44, ID 435 - Device Changed (Different Type)
Cause
•
The option board in slot E was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
•
Reset the fault. Set the option board parameters again.
8.2.29.6 Fault Code 44, ID 436 - Device Changed (Different Type)
Cause
•
The power configuration has changed. The power unit resets and initializes to a different configuration.
Troubleshooting
•
Wait until the power unit is reset.
8.2.30 Fault Code 45 - Device Added (Different Type)
8.2.30.1 Fault Code 45, ID 441 - Device Added (Different Type)
Cause
•
There is a new power unit of a different type. Parameters are not available in the settings.
Troubleshooting
•
Reset the fault. The drive reboots after you reset the fault.
•
Set the power unit parameters again.
8.2.30.2 Fault Code 45, ID 442 - Device Added (Different Type)
Cause
•
A new option board, that you have not used before in the same slot, was put in slot B. No parameter settings are saved.
Troubleshooting
•
Set the option board parameters again.