Precharge Monitoring - Danfoss VACON 3000 Application Manual

Table of Contents

Advertisement

VACON® 3000
Application Guide
Table 127: Data Out Monitoring
Index
Monitoring value
V2.8.8.1
FB Data Out 1
V2.8.8.2
FB Data Out 2
V2.8.8.3
FB Data Out 3
V2.8.8.4
FB Data Out 4
V2.8.8.5
FB Data Out 5
V2.8.8.6
FB Data Out 6
V2.8.8.7
FB Data Out 7
V2.8.8.8
FB Data Out 8
V2.8.8.9
FB Data Out 9
V2.8.8.10
FB Data Out 10
V2.8.8.11
FB Data Out 11
V2.8.8.12
FB Data Out 12
V2.8.8.13
FB Data Out 13
V2.8.8.14
FB Data Out 14
V2.8.8.15
FB Data Out 15
V2.8.8.16
FB Data Out 16

5.4.6 Precharge Monitoring

Table 128: Precharge Monitoring Values
Index
Monitoring value
V2.10.1
Precharge state
V2.10.2
Precharge inhibit
V2.10.3
Precharge error flags
100 | Danfoss A/S © 2021.09
Unit
Unit
Scale
ID
1
3510
1
3511
1
3568
Scale
ID
Description
1
866
1
867
1
868
1
869
1
870
1
871
1
872
1
873
1
245
1
246
1
247
1
248
1
249
1
250
1
251
1
252
Description
0 = Reset
1 = Failed
2 = Not Ready
3 = Ready
4 = Charging
5 = Synchronizing
6 = Contactor Close
7 = Stabilizing
8 = Operational
9 = Loaded
b0 = Software
b1 = Main Pilot Open TO
b2 = Mx Open TO
b3 = PC Contactor Open TO
b4 = DC-link Discharge TO
b5 = Front End Fault Clear TO
b6 = DC-link Overvoltage
AB319735759636en-000101 / DPD01822
AFE Application

Advertisement

Table of Contents
loading