VACON® 3000
Application Guide
7.182 (ID 739) Temperature Signal 1
Location in the menu:
INU application: P3.9.6.1
AFE application: P2.8.2.1
Use this parameter to select the temperature input signals that are supervised.
The maximum value is taken from the set signals and used for alarm and fault triggering.
Only the 6 first temperature inputs are supported (the boards from slot A to slot E).
7.183 (ID 740) Fault Limit Response 1
Location in the menu:
INU application: P3.9.6.4
AFE application: P2.8.2.4
Use this parameter to select the response of the drive to 'Temperature' fault.
7.184 (ID 741) Alarm Limit 1
Location in the menu:
INU application: P3.9.6.2
AFE application: P2.8.2.2
Use this parameter to set the temperature alarm limit.
Only the inputs that are set with parameter ID 739 are compared.
7.185 (ID 742) Fault Limit 1
Location in the menu:
INU application: P3.9.6.3
AFE application: P2.8.2.3
Use this parameter to set the temperature fault limit.
Only the inputs that are set with parameter ID 739 are compared.
7.186 (ID 744) Response to Quick Stop Fault
Location in the menu:
INU application: P3.9.5.4
Use this parameter to select the response of the drive to a 'Quick Stop' fault. If the quick stop command is given from DI or Fieldbus,
a quick stop fault occurs.
With the quick stop function, it is possible stop the drive in an unusual procedure from I/O or Fieldbus in unusual conditions. When
the quick stop function is active, it is possible make the drive decelerate and stop. It is possible to program an alarm or fault to put a
mark in the fault history that there was a request for a quick stop.
Do not use the quick stop function as an emergency stop. An emergency stop must stop the power supply to the motor. The
quick stop function does not do this.