VACON® 3000
Application Guide
7.72 (ID 421) Preset Frequency Selection 3
Location in the menu:
INU application: P3.3.3.11 and P3.5.1.22
Use this parameter to select the digital input signal that is used as a selector for the preset frequencies. This parameter is a binary
selector for Preset speeds (0–7). See parameters P3.3.3.1 to P3.3.3.8.
You can use the Preset frequencies function in processes where more than 1 fixed frequency reference is necessary. There are 8
preset frequency references available.
To apply Preset frequencies 1 to 7, connect a digital input to these functions with the instructions in
Inputs.
7.73 (ID 423) Control Signal 1 B
Location in the menu:
INU application: P3.5.1.4
Use this parameter to select the digital input signal (Control Signal 1) that starts and stops the drive when the control place is I/O B.
7.74 (ID 424) Control Signal 2 B
Location in the menu:
INU application: P3.5.1.5
Use this parameter to select the digital input signal (Control Signal 2) that starts and stops the drive when the control place is I/O B.
7.75 (ID 425) I/O B Control Force
Location in the menu:
INU application: P3.5.1.7
Use this parameter to select the digital input signal that switches the control place from I/O A to I/O B.
7.76 (ID 431) Setpoint Source 2 Selection
Location in the menu:
INU application: P3.12.2.8
Use this parameter to select the source of the PID setpoint signal. The AIs and the ProcessDataIn are handled as percentages (0.00–
100.00%) and scaled according to the setpoint minimum and maximum.
The ProcessDataIn signals use 2 decimals.
If temperature inputs are selected, the values of parameters P3.12.1.5 Process Unit Minimum and P3.12.1.6 Process Unit Maximum
must be set to correspond to the scale of the temperature measurement board: Process Unit Minimum = -50 °C and Process Unit
Maximum = 200 °C.
7.77 (ID 434) Control Signal 3 A
Location in the menu:
INU application: P3.5.1.3
AFE application: P3.5.1.3
BCU application: P3.4.1.3
Use this parameter to select the digital input signal (Control Signal 3) that starts and stops the drive when the control place is I/O A.
7.78 (ID 435) Control Signal 3 B
Location in the menu:
INU application: P3.5.1.6
Use this parameter to select the digital input signal (Control Signal 3) that starts and stops the drive when the control place is I/O B.
7.79 (ID 451) Joystick Signal Selection
Location in the menu:
INU application: P3.3.5.1
Danfoss A/S © 2021.09
Parameter descriptions
3.3 Programming of Digital
AB319735759636en-000101 / DPD01822 | 179