8.2.23.4 Fault Code 37, ID 364 - Device Changed (Same Type)
Cause
•
The option board in slot D was replaced by a new one that you have used before in the same slot. The device is ready to be
used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
8.2.23.5 Fault Code 37, ID 365 - Device Changed (Same Type)
Cause
•
The option board in slot E was replaced by a new one that you have used before in the same slot. The device is ready to be used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
8.2.24 Fault Code 38 - Device Added (Same Type)
8.2.24.1 Fault Code 38, ID 372 - Device Added (Same Type)
Cause
•
An option board was put into slot B. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
8.2.24.2 Fault Code 38, ID 373 - Device Added (Same Type)
Cause
•
An option board was put into slot C. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
8.2.24.3 Fault Code 38, ID 374 - Device Added (Same Type)
Cause
•
An option board was put into slot D. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
8.2.24.4 Fault Code 38, ID 375 - Device Added (Same Type)
Cause
•
An option board was put into slot E. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
8.2.25 Fault Code 39 - Device Removed
8.2.25.1 Fault Code 39, ID 382 - Device Removed
Cause
•
An option board was removed from slot A or B.
Troubleshooting
•
The device is not available. Reset the fault.