7.28 (ID 131) I/O Control Reference B Selection
Location in the menu:
INU application: P3.3.1.6
Use this parameter to select the reference source when the control place is I/O B. See P3.3.1.5 for more information. It is possible to
force the I/O B control place to be active only with a digital input (P3.5.1.7).
7.29 (ID 132) PID Derivation Time
Location in the menu:
INU application: P3.12.1.3
Use this parameter to adjust the derivation time of the PID controller. If this parameter is set to 1.00 s, a change of 10% in the error
value during 1.00 s causes the controller output to change by 10.00%.
7.30 (ID 167) Keypad Setpoint 1
Location in the menu:
INU application: P3.12.2.1
Use this parameter to set the setpoint value of the PID controller when the setpoint source is Keypad SP. The value of this parameter
is given in the selected process unit.
7.31 (ID 168) Keypad Setpoint 2
Location in the menu:
INU application: P3.12.2.2
Use this parameter to set the setpoint value of the PID controller when the setpoint source is Keypad SP. The value of this parameter
is given in the selected process unit.
7.32 (ID 172) Remote Control Place
Location in the menu:
INU application: P3.2.1
AFE application: P3.4.1
BCU application: P3.3.1
Use this parameter to select the remote control place (start/stop). Use this parameter to change back to remote control from VA-
CON
Live, for example if the control panel is broken.
®
7.33 (ID 180) Preset Frequency 0
Location in the menu:
INU application: P3.3.3.1
Use this parameter to set the preset frequency reference when the preset frequencies function is used. Select the preset frequencies
with the digital input signals.
7.34 (ID 181) Remote to Local Function
Location in the menu:
INU application: P3.2.10
AFE application: P3.4.7
Use this parameter to set the selection of copy settings when you go from Remote to Local (keypad) control.
Selection number
0
1
2
Danfoss A/S © 2021.09
Selection name
Keep Run
Keep Run & Reference
Stop
Parameter descriptions
Description
AB319735759636en-000101 / DPD01822 | 161