8.2.33.22 Fault Code 49, ID 922 - Pre-charge
Cause
The AFE was stopped while the INU was in operation.
Troubleshooting
Always stop the INU before shutting down the AFE.
8.2.33.23 Fault Code 49, ID 923 - Pre-charge
Cause
The front end could not keep up the DC-link voltage stabilization.
AFE or DFE voltage regulation could not be maintained.
Troubleshooting
Check the DC voltage control parameters and the synchronous current controller parameters.
8.2.33.24 Fault Code 49, ID 924 - Pre-charge
Cause
Parameter settings changed after the pre-charge sequence was activated.
Troubleshooting
Do not change the pre-charge configuration after starting the pre-charge sequence.
8.2.33.25 Fault Code 49, ID 925 - Pre-charge
Cause
The parameter settings are not valid.
Troubleshooting
Do not select the test modes "disable mains contactor" and "dry run" at the same time.
8.2.33.26 Fault Code 49, ID 926 - Pre-charge
Cause
Test mode activated while grid voltage is connected.
Troubleshooting
Do not select the "dry run" test mode while grid voltage is connected.
8.2.33.27 Fault Code 49, ID 927 - Pre-charge
Cause
The INU had a fault during the pre-charge sequence.
Troubleshooting
Check the INU status.
8.2.33.28 Fault Code 49, ID 928 - Pre-charge
Cause
The pre-charge transformer contactor closed unexpectedly after the pre-charge sequence was completed.
Troubleshooting
Check the pre-charge contactor wiring.
8.2.33.29 Fault Code 49, ID 930 - Pre-charge
Cause
Breaker enable was lost while the precharge output was active.
Troubleshooting
298 | Danfoss A/S © 2021.09