Fault Code 3 - Earth Fault - Danfoss VACON 3000 Application Manual

Table of Contents

Advertisement

VACON® 3000
Application Guide
8.2.2.4 Fault Code 2, ID 14 - DC- Overvoltage
Cause
The negative DC-link voltage is higher than the limits.
too short a deceleration time
high overvoltage spikes in the supply
Troubleshooting
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
Use a brake chopper. It is available as an option.
Activate the overvoltage controller.
Check the input voltage.
8.2.2.5 Fault Code 2, ID 16 - DC-Link Overvoltage
Cause
The DC-link voltage is too high for the motor.
Troubleshooting
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
Use a brake chopper. It is available as an option.
Activate the overvoltage controller.
Check the input voltage.

8.2.3 Fault Code 3 - Earth Fault

8.2.3.1 Fault Code 3, ID 20 - Earth Fault (Hardware Fault)
Cause
The ground current sensor has detected a too high current flowing to the ground or the current measurement has detected that
the sum of output phase currents is not zero (0 A).
an insulation malfunction in the cables or the motor
a filter (dU/dt, sine) malfunction
Troubleshooting
Check the motor cables and the motor.
Check the filters.
8.2.3.2 Fault Code 3, ID 21 - Earth fault (Software Fault)
Cause
The ground current sensor has detected a too high current flowing to the ground or the current measurement has detected that
the sum of output phase currents is not zero (0 A).
an insulation malfunction in the cables or the motor
a filter (dU/dt, sine) malfunction
Troubleshooting
Check the motor cables and the motor.
Check the filters.
8.2.3.3 Fault Code 3, ID 22 - Ground Fault
Cause
The DC link neutral to ground voltage is higher than the fault level.
Troubleshooting
Check the motor cables and the motor.
Check the filters.
Danfoss A/S © 2021.09
Fault tracing
AB319735759636en-000101 / DPD01822 | 271