Danfoss VACON 3000 Application Manual page 176

Table of Contents

Advertisement

VACON® 3000
Application Guide
INU application: P3.5.1.1
AFE application: P3.5.1.1
BCU application: P3.4.1.1
Use this parameter to select the digital input signal (Control Signal 1) that starts and stops the drive when the control place is I/O A
(FWD).
7.59 (ID 404) Control Signal 2 A
Location in the menu:
INU application: P3.5.1.2
AFE application: P3.5.1.2
BCU application: P3.4.1.2
Use this parameter to select the digital input signal (Control Signal 2) that starts and stops the drive when the control place is I/O A
(REV).
7.60 (ID 405) External Fault Close
Location in the menu:
INU application: P3.5.1.11
AFE application: P3.5.1.6
BCU application: P3.4.1.4
Use this parameter to select the digital input signal that activates an external fault.
7.61 (ID 406) External Fault Open
Location in the menu:
INU application: P3.5.1.12
AFE application: P3.5.1.7
BCU application: P3.4.1.5
Use this parameter to select the digital input signal that activates an external fault.
7.62 (ID 407) Run Enable
Location in the menu:
INU application: P3.5.1.15
AFE application: P3.5.1.10
BCU application: P3.4.1.7
Use this parameter to select the digital input signal that sets the drive to Ready state. When the contact is OPEN, the start of the
motor is disabled. When the contact is CLOSED, the start of the motor is enabled.
The state of the drive remains in 'Not Ready' if the state of this signal is 'opened'. If the Run Enable signal is used for stopping the
drive, the drive will always coast to stop regardless of the selection in parameter ID 506 Stop Function.
7.63 (ID 408) Ramp 2 Selection
Location in the menu:
INU application: P3.4.2.4 and P3.5.1.18
Use this parameter to select the digital input signal that selects the ramp time to be used.
Selection number
0
1
7.64 (ID 410) Keypad Control Force
Location in the menu:
176 | Danfoss A/S © 2021.09
Selection name
Description
OPEN
Ramp 1 Shape, Acceleration Time 1, and Deceleration Time 1
CLOSED
Ramp 2 Shape, Acceleration Time 2, and Deceleration Time 2
Parameter descriptions
AB319735759636en-000101 / DPD01822

Advertisement

Table of Contents
loading

Table of Contents