VACON® 3000
Application Guide
Selection num-
Selection name
ber
2
Output frequency
3
Frequency reference
4
Motor speed
5
Output current
6
Motor torque
7
Motor power
8
Motor voltage
9
DC-link voltage
10
Fieldbus Process Data In 1
11
Fieldbus Process Data In 2
12
Fieldbus Process Data In 3
13
Fieldbus Process Data In 4
14
Fieldbus Process Data In 5
15
Fieldbus Process Data In 6
16
Fieldbus Process Data In 7
17
Fieldbus Process Data In 8
7.579 (ID 10051) AO1 Filter Time
Location in the menu:
INU application: P3.5.4.1.2
AFE application: P3.5.4.1.2
BCU application: P3.4.4.1.2
Use this parameter to set the filtering time for the analog signal. The filtering function is disabled when the filtering time is 0. See ID
378.
7.580 (ID 10052) AO1 Minimum
Location in the menu:
INU application: P3.5.4.1.3
AFE application: P3.5.4.1.3
BCU application: P3.4.4.1.3
Use this parameter to change the range of the analog output signal. For example, if '4 mA' is selected, the range of analog output
signal is 4...20 mA. Select the signal type (current/voltage) with the DIP switches. The analog output scaling is different in ID 10053.
See also ID 379.
7.581 (ID 10053) AO1 Minimum Scale
Location in the menu:
INU application: P3.5.4.1.4
AFE application: P3.5.4.1.4
BCU application: P3.4.4.1.4
Danfoss A/S © 2021.09
Description
The actual output frequency from 0 to Maximum frequency reference.
The actual frequency reference from 0 to Maximum frequency reference.
The actual motor speed from 0 to Motor nominal speed.
The output current of the drive from 0 to Motor nominal current.
The actual motor torque from 0 to motor nominal torque (100%).
The actual motor power from 0 to Motor nominal power (100%).
The actual motor voltage from 0 to Motor nominal voltage.
The actual DC-link voltage 0...1000 V.
Fieldbus Process Data In 1: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 2: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 3: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 4: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 5: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 6: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 7: 0...10000 (this agrees with 0... 100.00%).
Fieldbus Process Data In 8: 0...10000 (this agrees with 0... 100.00%).
Parameter descriptions
AB319735759636en-000101 / DPD01822 | 263