VACON® 3000
Application Guide
8.2.41 Fault Code 59 - Communication
8.2.41.1 Fault Code 59, ID 590 - Communication
Cause
The Source2 unit cannot connect to the Source3 unit.
Troubleshooting
Check the power unit connections.
8.2.42 Fault Code 61 - Speed Error Fault
8.2.42.1 Fault Code 61, ID 1061 - Speed Error Fault
Cause
The difference between encoder frequency and output frequency exceeds the fault limit.
Troubleshooting
Check the encoder and encoder connections.
8.2.43 Fault Code 63 - Quick Stop
8.2.43.1 Fault Code 63, ID 1063 - Quick Stop Fault
Cause
The quick stop function is activated by digital input signal or from fieldbus.
Troubleshooting
Find the cause for the quick stop activation. After you find it, correct it. Reset the fault and restart the drive.
See parameter Quick Stop Activation (ID 1213) and the quick stop parameters.
8.2.43.2 Fault Code 63, ID 1363 - Quick Stop Alarm
Cause
The quick stop function is activated by digital input signal or from fieldbus.
Troubleshooting
Find the cause for the quick stop activation. After you find it, correct it. Reset the fault and restart the drive.
See parameter Quick Stop Activation (ID 1213) and the quick stop parameters.
8.2.44 Fault Code 65 - PC Communication Fault
8.2.44.1 Fault Code 65, ID 1065 - PC Communication Fault
Cause
The data connection between the PC and the drive is defective.
Troubleshooting
Check the installation, cable, and terminals between the PC and the drive.
302 | Danfoss A/S © 2021.09
Fault tracing
AB319735759636en-000101 / DPD01822