VACON® 3000
Application Guide
INU application: P3.17.2.1.3
AFE application: P3.3.2.1.5
Use this parameter to enable the main contactor/breaker feedback on the MV star DIN2 input.
7.388 (ID 3402) Enable KMX Feedback MVS DIN3
Location in the menu:
INU application: P3.17.2.1.4
AFE application: P3.3.2.1.6
Use this parameter to enable the main contactor/breaker pilot relay feedback on the MV star DIN3 input.
7.389 (ID 3403) MV Star Relay Configuration
Location in the menu:
INU application: P3.17.1.1
AFE application: P3.3.1.1
Use this parameter to set the MSC output configuration mask.
7.390 (ID 3404) Aux14 KPC Feedback Configuration
Location in the menu:
INU application: P3.17.2.1.5
AFE application: P3.3.2.1.7
Use this parameter to set the input configuration for KPC Status.
4x (per byte) aux DIN number 1–40.
7.391 (ID 3405) Aux14 MX Feedback Configuration
Location in the menu:
INU application: P3.17.2.1.6
AFE application: P3.3.2.1.8
Use this parameter to set the input configuration for MX Status.
4x (per byte) aux DIN number 1–40.
7.392 (ID 3406) Aux14 KMX Feedback Configuration
Location in the menu:
INU application: P3.17.2.1.7
AFE application: P3.3.2.1.9
Use this parameter to set the input configuration for KMX Status.
4x (per byte) aux DIN number 1–40.
7.393 (ID 3407) Aux1A Relay Configuration
Location in the menu:
INU application: P3.17.1.2
AFE application: P3.3.1.2
Use this parameter to set the AUX 0 output configuration mask.
7.394 (ID 3550) Power On
Location in the menu:
INU application: P3.5.1.34 and P3.17.2.2.1
AFE application: P3.3.2.2.1 and P3.5.1.15
Use this parameter to select the digital input signal for the Power On state of the AC drive. Pulse close starts the power on sequence.