8.2.33.2 Fault Code 49, ID 902 - Pre-charge
Cause
Main contactor open timeout.
Troubleshooting
Check the main contactor auxiliary contact wires.
8.2.33.3 Fault Code 49, ID 903 - Pre-charge
Cause
Pre-charge transformer contactor open timeout.
Troubleshooting
Check the pre-charge contactor auxiliary contact wires.
8.2.33.4 Fault Code 49, ID 904 - Pre-charge
Cause
DC link discharge timeout.
DC link discharge time exceeded the expected discharge time.
Troubleshooting
Check the mains contactor state and pre-charge wires.
8.2.33.5 Fault Code 49, ID 905 - Pre-charge
Cause
Front-end fault clear timeout.
Troubleshooting
If the INU controls the pre-charge, make sure that the AFE does not have a fault. If there is a fault, the pre-charge cannot contin-
ue.
8.2.33.6 Fault Code 49, ID 906 - Pre-charge
Cause
DC-link overvoltage. The pre-charge control sensed an overvoltage.
Troubleshooting
Check the AFE control signal wires and that the fieldbus connection is active.
8.2.33.7 Fault Code 49, ID 907 - Pre-charge
Cause
Front-end PLL phase lock lost. The PLL lost the synchronization during the operation.
Troubleshooting
Make sure that there is no input phase or voltage missing during operation.
8.2.33.8 Fault Code 49, ID 908 - Pre-charge
Cause
The front end had a fault after it reached the ready state. This fault applies only when the INU controls the pre-charge.
Troubleshooting
8.2.33.9 Fault Code 49, ID 909 - Pre-charge
Cause
The main contactor closes before the pre-charge control command.
Troubleshooting
Check the main contactor actuation circuit wires and the feedback wires.
Danfoss A/S © 2021.09
Fault tracing
AB319735759636en-000101 / DPD01822 | 295