VACON® 3000
Application Guide
8.2.55 Fault Code 112 - Temperature Input Fault 2
8.2.55.1 Fault Code 112, ID 1317 - Temperature Fault 2
Cause
1 or more of the temperature input signals (set in parameter ID 763) is higher than the alarm limit (parameter ID 764).
Troubleshooting
Find the cause of the temperature rise.
Check the parameters in the Temperature Input Fault 2 menu.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
8.2.55.2 Fault Code 112, ID 1318 - Temperature Fault 2
Cause
1 or more of the temperature input signals (set in parameter ID 763) is higher than the fault limit (parameter ID 765).
Troubleshooting
Find the cause of the temperature rise.
Check the parameters in the Temperature Input Fault 2 menu.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
8.2.56 Fault Code 114 - User Defined Fault 1
8.2.56.1 Fault Code 114, ID 1114 - User Defined Fault 1
Cause
This user-defined fault was activated either from a digital input, fieldbus, the drive customizer, or a time channel.
Troubleshooting
See parameter menu User Defined Fault 1 to find out the source of the fault activation.
8.2.57 Fault Code 115 - User Defined Fault 2
8.2.57.1 Fault Code 115, ID 1115 - User Defined Fault 2
Cause
This user-defined fault was activated either from a digital input, fieldbus, the drive customizer, or a time channel.
Troubleshooting
See parameter menu User Defined Fault 2 to find out the source of the fault activation.
8.2.58 Fault Code 200 - Precharge
8.2.58.1 Fault Code 200, ID 1721 - MCB/Interlock Fault
Cause
MCB is lost or interlock is required for power-on.
Troubleshooting