Use this parameter to scale the analog output signal. The scaling values (min and max) are given in the process unit that is specified
by the selection of the AO function.
7.582 (ID 10054) AO1 Maximum Scale
Location in the menu:
INU application: P3.5.4.1.5
AFE application: P3.5.4.1.5
BCU application: P3.4.4.1.5
Use this parameter to scale the analog output signal. The scaling values (min and max) are given in the process unit that is specified
by the selection of the AO function.
For example, you can select the output frequency of the drive for the contents of the analog output signal, and set parameters ID
10053 and ID 10054 between 10 and 40 Hz. Then the output frequency of the drive changes between 10 and 40 Hz, and the analog
output signal changes between 0 and 20 mA.
A
[%]
100%
20 mA
50%
10 mA
0%
0 mA
10 Hz
0 Hz
Illustration 53: Scaling of the AO1 signal
A
Analog output signal
B
AO min scale
C
AO max scale
7.583 (ID 11001) RO1 Function
Location in the menu:
INU application: P3.5.3.2.1
AFE application: P3.5.3.2.1
BCU application: P3.4.3.2.1
Use this parameter to select a function or a signal that is connected to the relay output.
264 | Danfoss A/S © 2021.09
B
40 Hz
D
C
D
Max freq reference
E
Output frequency
Parameter descriptions
[Hz]
E
AB319735759636en-000101 / DPD01822