VACON® 3000
Application Guide
Parameter descriptions
Use this parameter to set the limit for Flux ready. The Flux ready bit is enabled in CW when rotor flux is above this limit for sensorless
modes.
7.514 (ID 4020) Closed Loop Motoring Torque Limit
Location in the menu: P3.1.3.7
Use this parameter to set the additional torque limit for the motoring torque direction between 0.0–300.0%. 100% equals to motor
nominal torque.
7.515 (ID 4021) Closed Loop Generative Torque Limit
Location in the menu: P3.1.3.8
Use this parameter to set the additional torque limit for the generative torque direction between 0.0–300.0%. 100% equals to motor
nominal torque.
7.516 (ID 4022) Closed Loop Motoring Power Limit
Location in the menu: P3.1.3.9
Use this parameter to set the motoring electric power limit between 0.0–300.0%. 100% equals to motor nominal power (√3×U
×I
).
n
n
7.517 (ID 4023) Closed Loop Generating Power Limit
Location in the menu: P3.1.3.10
Use this parameter to set the generating electric power limit between 0.0–300.0%. 100% equals to motor nominal power
(√3×U
×I
).
n
n
7.518 (ID 4025) Speed Error Filter
Location in the menu: P3.1.2.4.8
Use this parameter to set the filtering time for the speed reference and the actual speed error.
7.519 (ID 4026) Motor Speed Filter Time
Location in the menu: P3.11.6
Use this parameter to set the Motor Speed Filter Time. A value higher than 0 activates the low pass filtering function for this signal.
The filtering time is the time it takes to reach 63% of a step change in the signal.
7.520 (ID 4027) FW Control Kp
Location in the menu: P3.1.5.12
Use this parameter to set a value for FW Control Kp in percent.
7.521 (ID 4028) FW Control Ti
Location in the menu: P3.1.5.13
Use this parameter to set a value for FW Control Ti in seconds.
7.522 (ID 4030) Speed Error Limit
Location in the menu: P3.9.11.2
Use this parameter to set the limit when the speed error fault is generated. The limit is the maximum difference between the speed
reference and the encoder speed. When the difference goes outside this limit, a fault occurs.
7.523 (ID 4031) Speed Error Delay
Location in the menu: P3.9.11.3
Use this parameter to set the delay after which the AC drive goes to FAULT state when there is a speed error.
7.524 (ID 4032) Speed Error Fault Response
Location in the menu: P3.9.11.1
Use this parameter to select the response of the drive to the speed error (fault ID 1061).
254 | Danfoss A/S © 2021.09
AB319735759636en-000101 / DPD01822