Parameter descriptions
7.254 (ID 1240) Jogging reference 2
Location in the menu: P3.3.6.5
Use this parameter to set the frequency references for the jogging function. With the parameters P3.3.6.4 and P3.3.6.5, it is possible
to set the frequency references for the jogging function. The references are bi-directional. A reverse command does not affect the
direction of the jogging references. The reference for the forward direction has a positive value, and the reference for the reverse
direction has a negative value. The jogging function can be activated with digital input signals or from Fieldbus in bypass mode
with Control Word bits 10 and 11.
7.255 (ID 1244) Torque Reference Filter Time
Location in the menu: P3.3.2.4
Use this parameter to set the filtering time for the final torque reference.
7.256 (ID 1250) Flux Reference
Location in the menu: P3.1.5.11
Use this parameter to adjust the flux reference. The value 100% means a nominal flux.
7.257 (ID 1256) Quick Stop Deceleration Time
Location in the menu: P3.9.5.3
Use this parameter to set the time that is necessary for the output frequency to decrease from maximum frequency to 0 when a
quick stop command is given. The value of this parameter is applied only when the quick stop mode parameter is set to 'Quick Stop
Deceleration time'.
7.258 (ID 1257) Jogging Ramp
Location in the menu: P3.3.6.6
Use this parameter to set the ramp time when jogging is active. This parameter gives the acceleration and deceleration times when
the Jogging function is active.
7.259 (ID 1276) Quick Stop Mode
Location in the menu: P3.9.5.1
Use this parameter to select how the drive stops when the quick stop command is given from DI or Fieldbus.
7.260 (ID 1285) Positive Frequency Reference Limit
Location in the menu: P3.3.1.3
Use this parameter to set the final frequency reference limit for the positive direction.
7.261 (ID 1286) Negative Frequency Reference Limit
Location in the menu: P3.3.1.4
Use this parameter to set the final frequency reference limit for the negative direction. Use this parameter for example to prevent
the motor from running in the reverse direction.
7.262 (ID 1287) Motor Torque Limit
Location in the menu: P3.1.3.2
Use this parameter to set the maximum torque limit of the motoring side.
7.263 (ID 1288) Generator Torque Limit
Location in the menu: P3.1.3.3
Use this parameter to set the maximum torque limit of the generating side.
7.264 (ID 1289) Motor Power Limit
Location in the menu: P3.1.3.4
Use this parameter to set the maximum power limit of the motoring side.
7.265 (ID 1290) Generator Power Limit
Location in the menu: P3.1.3.5