8.2.51 Fault Code 78 - Identification Ongoing
8.2.51.1 Fault Code 78, ID 1078 - Identification Ongoing
Cause
The drive is running the identification for the motor.
Troubleshooting
You can stop the identification run at any time by removing the start command. When the identification run is completed, a
new start command is needed to start the drive.
8.2.52 Fault Code 80 - Fieldbus Watchdog Fault
8.2.52.1 Fault Code 80, ID 1080 - FB Watchdog Fault
Cause
There is no communication between the fieldbus master and the fieldbus follower.
Troubleshooting
Check the installation and the fieldbus master.
8.2.53 Fault Code 84 - Overspeed Error
8.2.53.1 Fault Code 84, ID 1084 - Overspeed Error
Cause
The motor speed is over the speed limit.
Troubleshooting
8.2.54 Fault Code 111 - Temperature Input Fault 1
8.2.54.1 Fault Code 111, ID 1315 - Temperature Fault 1
Cause
1 or more of the temperature input signals (set in parameter ID 739) is higher than the alarm limit (parameter ID 741).
Troubleshooting
Find the cause of the temperature rise.
Check the parameters in the Temperature Input Fault 1 menu.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
8.2.54.2 Fault Code 111, ID 1316 - Temperature Fault 1
Cause
1 or more of the temperature input signals (set in parameter ID 739) is higher than the fault limit (parameter ID 742).
Troubleshooting
Find the cause of the temperature rise.
Check the parameters in the Temperature Input Fault 1 menu.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.