8.2.30.3 Fault Code 45, ID 443 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot C. No parameter settings are saved.
Troubleshooting
Set the option board parameters again.
8.2.30.4 Fault Code 45, ID 444 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot D. No parameter settings are saved.
Troubleshooting
Set the option board parameters again.
8.2.30.5 Fault Code 45, ID 445 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot E. No parameter settings are saved.
Troubleshooting
Set the option board parameters again.
8.2.31 Fault Code 46 - Real Time Clock
8.2.31.1 Fault Code 46, ID 662 - Real Time Clock
Cause
The voltage of the RTC battery is low.
Troubleshooting
Replace the battery.
8.2.32 Fault Code 47 - Software Update
8.2.32.1 Fault Code 47, ID 661 - Software Update
Cause
A software update is in progress.
The software is updating from the control unit to the power unit.
Troubleshooting
No steps are necessary.
8.2.32.2 Fault Code 47, ID 663 - Software Updated
Cause
The software of the drive was updated, the full software package or an application.
Troubleshooting
No steps are necessary.
8.2.33 Fault Code 49 - Precharge
8.2.33.1 Fault Code 49, ID 901 - Pre-charge
Cause
Main contactor pilot relay open timeout.
Troubleshooting
Check the main contactor pilot relay wires.