INU application: P3.17.5.4
AFE application: P3.3.5.4
Use this parameter to enable the precharge synchronization test mode. When enabled, the main contactor is not commanded to
close.
Use this mode to check the phase order and scaling of the grid voltage feedback.
7.381 (ID 3355) Supply Voltage Select
Location in the menu:
Standard application: P3.1.3.11
Use this parameter to set the supply voltage definition.
Estimated.
Selected by parameter Set supply voltage (ID 1201).
7.382 (ID 3360) Enclosure Humidity and Temperature
Location in the menu:
INU application: P3.9.1.18
AFE application: P3.8.1.11
Use this parameter to set the response when a humidity or temperature switch detects an out of range limit in the enclosure.
7.383 (ID 3365) FB Coolant Decimal Places
Location in the menu:
INU application: P3.9.12.4
AFE application: P3.8.5.4
Use this parameter to select the number of decimal places used in the process data coolant temperature.
2D = 2 decimals, for example, 24.50.
1D = 1 decimal, for example, 24.5.
7.384 (ID 3366) Coolant Scale Minimum
Location in the menu:
INU application: P3.9.12.2
AFE application: P3.8.5.2
Use this parameter to set the temperature in °C, which corresponds to the minimum of the analog signal range. For example, 0 mA
corresponds to 0 °C.
7.385 (ID 3367) Coolant Scale Maximum
Location in the menu:
INU application: P3.9.12.3
AFE application: P3.8.5.3
Use this parameter to set the temperature in °C, which corresponds to the maximum of the analog signal range. For example, 20 mA
corresponds to 100 °C.
7.386 (ID 3400) Enable Precharge Feedback MVS DIN1
Location in the menu:
INU application: P3.17.2.1.2
AFE application: P3.3.2.1.4
Use this parameter to enable the precharge contactor feedback on the MV star DIN1 input.
7.387 (ID 3401) Enable MX Feedback MVS DIN2
Location in the menu:
Danfoss A/S © 2021.09
Parameter descriptions