Instruction Manual
®
VLT
4000 VT

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss VLT 4000 VT

  • Page 1 Instruction Manual ® 4000 VT...
  • Page 2: Table Of Contents

    Cables ........................36 Shielded/armored cables ..................36 High voltage test ....................37 Heat emission from VLT 4000 VT ................37 Grounding of shielded/armored control cables ............38 VLT 4000 VT enclosures ..................39 Tightening-up torque and screw sizes ..............45 Line connection ......................
  • Page 3 Calculation of resulting reference ................123 Extreme running conditions .................. 125 Peak voltage on motor ..................126 Derating for ambient temperature ................. 128 Efficiency ......................130 Definitions ......................132 Factory settings ....................134 Index ........................139 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 4: Introduction

    VLT 4000 VT Instruction Manual Software version: 1.0x This Instruction Manual can be used for all VLT 4000 VT, Adjustable Frequency Drives (AFD) with software version 1.0x. The software version number can be seen from parameter 624 Software version no.
  • Page 5: Safety Regulations

    Using VLT: wait at least 20 minutes for 200 and 400 V units wait at least 30 minutes for 525-600 V units Using VLT 4452-4652, 380-460 V: Wait at least 40 minutes! MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 6 Improper installation of the motor or the VLT may cause equipment failure, serious injury or death. Follow this manual and National Electrical Codes (NEC ) and local safety codes. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 7: Introduction To This Instruction Manual

    Programming: This section describes the control unit and the software parameters for the VLT 4000 VT. Also included is a guide to the Quick Setup menu, which allows you to get started on your application very quickly. All about VLT 4000 VT: This section gives information about status, warning and error messages from the VLT 4000 VT.
  • Page 8: Control Principle

    However, knowing the load at a given frequency in an installation is often a problem. This problem can be sol-ved by using a VLT 4000 VT with its integral Automatic Energy Optimization (AEO), which ensures optimum energy utilization. All VLT 4000 VT units feature this function as a factory setting, i.e.
  • Page 9: Serial Communication

    Serial communication allows monitoring, programming and controlling one or several units from a centrally placed computer. All VLT 4000 VT units have a RS 485 port as standard. 500-537 Serial communication NOTE Information on the use of RS 485 serial interface is not included in this manual.
  • Page 10: Unpacking And Ordering A Vlt Adjustable Frequency Drive (Afd)

    Use the following table to find out. The table can also be used for ordering a VLT 4000 VT. Type code ordering number string On the basis of your order, the VLT AFD is given an ordering number that can be seen from the nameplate on the unit.
  • Page 11 PF: Standard with 24 V supply and fuse RFI filter C20: Compact IP 20 CN1: Compact NEMA 1 R0: Without filter C54: Compact IP 54 R1: Class A1 filter R3: Class A1 and B filter MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 12 Application option Position: 23-25 No options Aux. relay option (1 relay) Relay card 4 relays Coating Position: 26-27 No coating With coating 1) Not available for power sizes from 4450 to 4600 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 13: Ordering Form Vlt 4000 Vt

    ® 4000 VT Ordering form VLT 4000 VT MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 14: Installation

    Terminal nos......................16, 17, 18, 19, 27, 29, 32, 33 Voltage level ......................0-24 V DC (PNP positive logics) Voltage level, logical "0" ........................... < 5 V DC Voltage level, logical "1" ......................... > 10 V DC MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 15 No. of programmable digital and analog outputs ....................2 Terminal nos..............................42, 45 Voltage level at digital/pulse output ...................... 0 - 24 V DC Minimum load to frame (terminal 39) at digital/pulse output ................600 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 16 Max. motor cable length, unshielded cable ....................1000 feet Max. motor cable length, shielded cable VLT 4011 380-460 V ..............330 feet Max. motor cable length, shielded cable VLT 4011 525-600 V ..............165 feet MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 17 • Temperature monitoring of heat-sink ensures that the VLT AFD cuts out if the temperature reaches 90°C for Chassis and NEMA 1. For NEMA 12, the cut-out temperature is 80°C. An overtemperature can only be reset when the temperature of the heat-sink has fallen below 60°C. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 18 • If there is a line fault, the VLT AFD is able to carry out a controlled deramping. • If a line phase is missing, the VLT AFD will cut out when a load is placed on the motor. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 19: Line Supply 3 X 200 - 240 V

    1. See section Fuses 2. American Wire Gauge 3. Measured using 100 ft. shielded motor cable at rated load and rated frequency. 4. Connection stud 1 x M8 / 2 x M8. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 20: Line Supply 3 X 380 - 460 V

    3 Measured using 100 feet shielded motor cable at rated load and rated frequency. 4 Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 21 3. Measured using 100 feet shielded motor cable at rated load and rated frequency. 4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 22 4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section. 5. DC connection 95 mm /AWG 3/0. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 23 Always comply with national and local regulations on min. cable cross-section. 5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus). MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 24 4. Always comply with national and local regulations on min. cable cross-section. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals. 5. Connection bolt power supply, motor and load sharing: M10 compression (lug), 2 x M8 (box lug) MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 25: Line Supply, 3 X 525 - 600 V

    Estimated power loss at max. load Enclosure IP 20 and NEMA 1 1. See section Fuses. 2. American Wire Gauge (AWG). 3. Measured using 100 ft screened motor cables at rated load and rated frequency. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 26 3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section. 4. Aluminum cables with cross section above 35 mm /AWG 2 must be connected by use of an Al-Cu connector. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 27 Always comply with national and local regulations on min. cable cross-section. 5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus). MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 28 Always comply with national and local regulations on min. cable cross-section. 5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus). MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 29: Fuses

    No. SRPK800 A 300 4202 rating plug No. SRPK800 A 400 4252 rating plug No. SRPK800 A 400 4302 rating plug No. SRPK800 A 500 4352 rating plug No. SRPK800 A 600 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 30 Not following the recommendation may result a circuit capable of supplying a maximum of 100000 in unnecessary damage of the drive in case of (symmetrical), 500 V/600 V maximum. malfunction. Fuses must be designed for protection in MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 31: Mechanical Dimensions

    47.6 16.5 14.7 45.4 4252 - 4402 62.5 16.5 14.7 60.4 aa: Min. air-space above enclosure to other parts. bb: Min. air-space below enclosure to other parts. With disconnect, add 1.73 in. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 32 ® 4000 VT Mechanical dimensions MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 33 ® 4000 VT Mechanical dimensions (cont.) Type H, Chassis, NEMA 1, NEMA 12 Type I, IP 00 Type J, Chassis, NEMA 1, NEMA 12 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 34: Mechanical Installation

    -55° C, derating of the VLT AFD will become relevant, see Derating for ambient temperature. The service life of the VLT AFD will be reduced if derating for ambient temperature is not taken into account. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 35 VLT 4102 - 4402, 525-600 V mats must be changed when they are dirty. VLT 4452 - 4652, 380-460 V 225/9.0 IP 00 above and below enclosure IP 21/IP 54 only above enclosure MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 36 This applies to both chassis, NEMA 1 and NEMA12 units. For accessing the VLT 4452-4652 VT it requires a minimum space of 22.8 inches in front of the VLT AFD. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 37: General Information About Electrical Installation

    HF impedance. This avoids having different HF voltages for the individual devices and avoids the risk of ra-dio interference currents running in connection cables that may be used between the devices. The radio interference will have been reduced. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 38: High Voltage Test

    Heat emission from VLT 4000 VT The tables in General technical data show the power loss P (W) from VLT 4000 VT. The maximum cooling air ϕ temperature t is 40° at 100% load (of rated value).
  • Page 39: Grounding Of Shielded/Armored Control Cables

    61. This terminal is connected to ground via an internal RC link. It is recommended to use twisted-pair cables to reduce the differential mode interference between the conductors. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 40: Vlt 4000 Vt Enclosures

    VLT 4006-4032, 200-240 V VLT 4006-4011, 380-460 V VLT 4016-4072, 380-460 V VLT 4006-4011, 525-600 V VLT 4016-4072, 525-600 V NEMA 12 Compact NEMA 1 VLT 4006-4011, 380-460 V VLT 4102-4122, 380-460 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 41 ® 4000 VT Compact IP 20 VLT 4102-4122, 380-460 V Compact NEMA 12 VLT 4102-4122, 380-460 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 42 VLT 4000 VT enclosures NEMA 12 VLT 4006-4032, 200-240 V Chassis VLT 4016-4072, 380-460 V Chassis VLT 4042-4062, 200-240 V NEMA 1 NEMA 12 VLT 4042-4062, 200-240 V VLT 4042-4062, 200-240 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 43 VLT 4152-4202, 380-460 V VLT 4102-4202, 525-600 V VLT 4102-4202, 525-600 V NEMA 1, NEMA 12 Chassis Disconnect, fuse, RFI Disconnect, fuse, RFI VLT 4252-4352, 380-460 V VLT 4252-4352, 380-460 V VLT 4252-4402, 525-600 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 44 Compact NEMA 1 / NEMA 12 without disconnect and fuse VLT 4452-4652 380-460 V Compact chassis without disconnect and fuse VLT 4452-4652 380-460 V Position of earth terminals, NEMA 1 / NEMA 12 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 45 VLT 4006-4032, 200-240 V Chassis/NEMA 1 VLT 4016-4122, 380-460 V VLT 4042-4062, 200-240 V VLT 4016-4072, 525-600 V NEMA 12 VLT 4006-4032, 200-240 V VLT 4016-4072, 380-460 V NEMA 12 - VLT 4042-4062, 200-240 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 46: Tightening-Up Torque And Screw Sizes

    4 mm VLT 4052-4072 53 in-lbs/6.0 Nm 5 mm VLT 4102-4402 168 in-lbs/19 Nm M10 (bolt) 1. IP 54 units with RFI filter line terminals 53 in-lbs/6 Nm 2. Allen screws (hexagon) MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 47: Motor Connection

    Ground connection. See Technical data for correct sizing of cable cross-sections. All types of three-phase asynchronous standard motors can be used with a VLT 4000 VT unit. Small-size motors are normally star-connected. (220/380 V, /Y). Large-size motors are delta-connected (380/660 VLT 4000 VT is able to control several motors /Y).
  • Page 48 If it is necessary to break the shield to install a motor isolator or motor contactor, the shield must be continued at the lowest possible HF impedance. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 49: Dc Bus Connection

    The power consumption is 15-50 W, depending on the load on the control card. NOTE Use 24 V DC supply of type PELV to ensure correct galvanic isolation (type PELV) on the control terminals of the VLT AFD. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 50: Switches 1-4

    The dipswitch is located on the control card. It is used for serial communication and external DC supply. Function The switching position shown is the factory setting. 04, 05 Relay output 1 can be used for indicating status and warnings. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 51 24 V DC supply. NOTE Please note that when Switch 4 is in position "OFF", the external 24 V DC supply is galvanically isolated from the VLT AFD. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 52 61, which is connected to the frame via an RC-link. Bus termination The bus must be terminated by a resistor network at both ends. For this purpose, set switches 2 and 3 on the control card for "ON". MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 53: Connection Example, Vlt 4000 Vt

    VLT AFD can be controlled and monitored for either reference, feedback or thermistor. See via serial communication. Analog inputs in parameter group 300. * These terminals can be programmed for other functions. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 54 Parameter 309 = Terminal 53, min. scaling Parameter 310 = Terminal 53, max. scaling - Parameter 314 = Reference [1] - Parameter 315 = Terminal 60, min. scaling - Parameter 316 = Terminal 60, max. scaling MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 55: Control Unit Lcp

    (Local Control Panel). This is a complete inter-face for unless this function has been programmed to beLocked operation and programming of the VLT 4000 VT. [1] via parameter 016 Lock for data change or via a The control panel is detachable and can - as digital input, parameters 300-307 Lock for data change.
  • Page 56: Indicator Lamps

    When alarm and/ or warning lamp is activated, and a a start signal is active on the control status or alarm text is displayed. terminals and/or the bus, the AFD will start. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 57 HAND indicates that control is via the local keys on the control unit. OFF means that the VLT AFD ignores all control commands and stops the motor. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 58 LOCAL indicates that the reference is determined via the [+/-] keys on the control panel. Display mode I: VLT 4000 VT offers different display modes de-pending Display mode II: on the mode selected for the VLT AFD. The figure This display mode makes it possible to have three...
  • Page 59 HAND LOCAL RUNNING AUTO REMOTE RUNNING With local reference Display mode IV Display mode II Keep the [DISPLAY MODE] key down REF% CURR.A POW.,KW 40.0 Hz AUTO REMOTE RUNNING Display mode III 175ZA697.10 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 60 600, Operating hours 601, Hours run 602, kWh counter 603, Number of power-ups 604, Number of overtemperatures 605, Number of overvoltages It is also possible to carry out initialization via parameter 620 Operating mode MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 61: Quick Menu

    Ramp Up Time reads ‘100 s.’ procedure as described for Quick Menu functions. 8. Press OK key to enter new value into drive controller. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 62: Programming

    The Setup configuration for switching between Setups. VLT 4000 VT has four Setups (parameter Setups) that can be programmed independently of each other. The active Setup can be selected in parameter 002 Active Setup.
  • Page 63: Setup Of User-Defined Readout

    The copying starts when the required copying function is a linear, square or cubed ratio. has been selected and the [OK] key has been pressed. The display indicates when copying is in progress. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 64 (FREQUENCY [%]) Motor current [A] (MOTOR CURRENT [A]) Power [kW] (POWER [KW]) Power [HP] (POWER [HP]) Output energy [kWh] (ENERGI [UNIT]) Hours run [Hours] (HOURS RUN [H]) User-defined readout [-] (CUSTOM READ.[UNITS]) MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 65 53. motor measured as effective value. Analog input 54 [V] states the voltage Power [HP] states the actual power consumed value on terminal 54. by the motor in HP. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 66 Hand start key on the control panel. Function: Description of choice: See the functional description for parameter 008 Small display readout. If Disable [0] is selected in this parameter, the [HAND START] key will be inactive. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 67 To restart, activate the key [HAND If Disable [0] is selected in this parameter, the START] or [AUTO START] by using the control panel . [RESET] key will be inactive. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 68 OFF/Stop [1] is selected. If Handstart or Autostart has been programmed for activation via the digital inputs, the motor will not be able to restart if OFF/Stop [1] is selected. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 69: Load And Motor 100-117

    0.25 HP (0.25 KW) [25] 0.5 HP (0.37 KW) [37] 0.75 HP (0.55 KW) [55] 1 HP (0.75 KW) [75] 1.5 HP (1.10 KW) [110] 2 HP (1.50 KW) [150] 3 HP (2.20 KW) [220] MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 70 Depends on the choice of motor. 220 V [220] Function: 230 V [230] The rated motor current I forms part of the AFD 240 V [240] calculations of torque and motor thermal protection. 380 V [380] MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 71 Automatic adaptation with LC-filter [2] if a LC-filter has the motor applied. This feature is used where the factory been placed between the VLT AFD and the motor. setting does not match requirements of the motor. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 72 This parameter enables a delay of the starting time start-up torque. This is used especially for small motors after the conditions for start have been fulfilled. (< 4.0 HP) connected in parallel, as they have a higher MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 73 Make sure not to supply too high a braking long, the motor can be damaged. current for too long.The motor will be damaged because of mechanical overload or the heat generated in the motor. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 74 NOTE The AFD is able to monitor the motor temperature In UL / cUL applications ETR provides class in two different ways: 20 motor overload profection in accordance with National Electrical Code. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 75: References And Limits 200-228

    Description of choice: Select the required output frequency range. 201 Output frequency low limit, f (MIN. FREQUENCY) Value: 0.0 - f 0.0 HZ Function: This is where to select the minimum output frequency. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 76: Reference Handling

    The unit of the local reference can be set either as Hz or as a percentage of the output frequency range. The unit is selected in parameter 011 Unit of local reference. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 77 -Par. 413 Minimum feedback Maximum reference is set if the motor speed is not - par. 205 Ref 0.000 to exceed the set value, regardless of whether the resulting reference is higher than Maximum reference. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 78: Reference Type

    When parameter 210 Reference type is set to Sum This function ensures that the AFD does not trip [0], one of the adjusted Preset references (par. 211- during deceleration if the ramp-down time set is too MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 79 -100.00 % - +100.00 % 0.00% (REF. FUNCTION) of the reference range/external reference Value: Function: Sum (SUM) Four different preset references can be programmed Relative (RELATIVE) in parameters 211-214 Preset reference. The External/preset (EXTERNAL/PRESET) MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 80 Description of choice: Set the required maximum output current I Description of choice: Enter the frequencies to be avoided. See also parameter 216 Frequency bypass, bandwidth. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 81 If the motor current is above the limit, I HIGH Par. 200 Output frequency range = 0-1000 Hz [1]. programmed in this parameter, the display shows parameter 223 - 1000 Hz 120.0 Hz a flashing CURRENT HIGH. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 82 Closed loop mode the unit is programmed in parameter 415 Process units. Description of choice: The lower signal limit, Ref , of the reference must be programmed within the normal working range of MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 83 The signal outputs can be programmed to generate a warning signal via terminal 42 or 45 and via the relay outputs. In Closed loop, the unit for the feedback is programmed in parameter 415 Process units. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 84: Inputs And Outputs 300-328

    (terminals 16-33). The functional options are given in the table on the previous page. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 85 Ramp-down time set in parameter 207. of Speed up or Speed down . The frozen reference is saved after a stop command and in case of line failure. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 86 . The frequency set in parameter 327 Pulse reference, max. frequency corresponds to parameter 205 Maximum reference, Ref Pulse feedback is selected if a pulse sequence (frequency) is selected as a feedback signal. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 87: Analog Inputs

    In the case of zone regulation, feedback signals must be selected as voltage inputs (terminals 53 and 54). See Feedback handling. A motor thermistor connected to terminals 53/54 must be double isolated to obtain PELV. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 88 Reference handling or Feedback handling. Value: See description of parameter 308. No operation Description of choice: Set the required voltage value. Function: This parameter chooses between the different functions available for the input, terminal 54. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 89 0.0 - 20.0 mA 20.0 mA time interval function), the time-out function in parameter 318 will be activated. Function: This parameter determines the signal value that corresponds to the maximum reference value, MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 90 - frozen at the present value [1] - overruled to stop [2] - overruled to jog frequency [3] - overruled to max. output frequency [4] - overruled to stop with subsequent trip [5]. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 91: Analog/Digital Outputs

    Output power, 0 - P [41] [41] ⇒4-20 mA (MOTOR POWER 4-20 mA) Output power, 0 - P [42] [42] ⇒0- 32000 p (MOTOR POWER PULSE) Output power (pulse sequence), 0 - P [43] [43] MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 92 Reversing. There is 24 V DC on the output when the Relay 123. This function is only used when a motor rotates counter-clockwise. When the mo-tor profibus option card is installed. rotates clockwise, the value is 0 V DC. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 93 Set the desired value. (AO 42 PULS SCALE) Value: 1 - 32000 Hz 5000 Hz Function: This parameter allows scaling of the pulse output signal. Description of choice: Set the desired value. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 94: Relay Outputs

    See description of [0] - [28] in Analog/digital outputs. Control word bit 11/12 , relay 1 and relay 2 can be activated via the serial communication. Bit 11 activates relay 1 and bit 12 activates relay 2. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 95 This is where the pulse value that must correspond Enter the desired value. to the maximum feedback value is set. The pulse fedback signal is connected via terminal 33. Description of choice: Set the desired feedback value. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 96: Application Functions 400-427

    "Reset" key or via a digital input. If the VLT AFD is to carry out an automatic reset and restart after a trip, select data value [1]-[9]. The motor may start without warning. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 97: Sleep Mode

    Flying via parameter 207 Ramp-down time . If the output Start function (parameter 402). frequency rises above the frequency set in parameter 404 Sleep frequency, the timer is reset. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 98 When the theoretical output frequency exceeds the preset value, the AFD restarts the motor. Description of choice: When the motor is running, the switching frequency is adjusted in parameter 407 Switching frequency, MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 99 411 Function at overtemperature below parameter 221 Warning: Low current. (FUNCT. OVERTEMP) Description of choice: Value: Trip (TRIP) In the case of a Trip [1], the VLT AFD will stop the motor. Autoderate & warning MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 100 Normally, feedback signals and thus feedback parameters are only used in Closed loop operation; in VLT 4000 VT units, however, the feedback parameters are also active in Open loop operation. In Open loop mode , the feedback parameters can be used to show a process value in the display.
  • Page 101 In Closed loop, the unit is also used as a unit for Minimum/Maximum reference and Minimum/ Maximum feedback, as well as Setpoint 1 and Setpoint 2. Description of choice: Select the required unit for the reference/feed- back signal. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 102: Pid For Process Control

    Reference type Terminal Parameters Pulse 17 or 29 301 or 305 Using the VLT 4000 VT, there is no need for extra Voltage 53 or 54 308, 309, 310 or modules to be installed. For example, only one 311, 312, 313...
  • Page 103 427, PID Lowpass filter time. Optimisation of the process regulator The basic settings have now been made; all that remains to be done is to optimize the proportional gain, the integration time and the differentiation time MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 104: Pid Overview

    Setpoint 1 in parameter 418. Depending on the feedback function selected in parameter In addition, the VLT 4000 VT has an integral calculator 417 Feedback function , a calculation will be made capable of converting a pressure signal into a "linear of the feedback signal with which the sum of the flow"...
  • Page 105 If Square root different calculation methods whenever two [1] is selected, the VLT AFD translates the feedback feedback signals are used. signal to a squared feedback value. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 106 It is possible to choose whether the process be added to parameter 419 Setpoint 2. regulator is to increase/reduce the output frequency MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 107 When the start signal comes, the AFD will react in the greater the error, the quicker the integrator frequency form of Open loop [0] following the ramp. Only when the contribution will increase. The integration time is the MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 108 Used in Closed loop [1] (parameter 100). MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 109: Service Functions 600-631

    Parameter 603 No. of cut-ins: Gives the number of cut-ins of supply voltage to the AFD. Parameter 604 No. of overtemps: Gives the number of overtemperature errors on the heat-sink of the AFD. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 110 This gives the latest log data for the output current. extreme right and to decimal code 1. The table can be used, e.g., for converting a decimal number into a binary code. For example, digital MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 111 (RESET KWH COUNT) [10] contains the oldest data value. If there is a trip on the VLT 4000 VT, it is possible Value: to see its cause, the time and possibly the values No reset (DO NOT RESET) for output current or output voltage.
  • Page 112 Setups with the exception of parameters connect 5-12; 500 Address, 501 Baud rate, 600-605 Operating connect 39-20-55; data and 615-617 Fault log. connect 42 - 60; Manual initialisation is another option.(See connect 45-53-54. Manual initialization). MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 113 This gives the identification number of the software’s database. Example: ID 1.14. Parameter 627 Nameplate: Power Nameplate: identification no.: This gives the identification number of the database of the unit. Example: ID 1.15. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 114: Electrical Installation Of The Relay Card

    This parameter allows a delay of the cut-in time To achieve double isolation, the plastic foil must be of relays 6/7/8/9 (terminals 1-2). mounted as shown in the drawing below. Description of choice: Enter the required value. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 115: All About Vlt 4000 Vt

    A freeze output command has been given, but the via the control terminals or via serial communication. motor will remain stopped until a Run permissive See also Display modes . signal is received via a digital input. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 116 AFD is out of operation. The cause may be noise on the line, motor or control cables, leading to a stop of the control card microprocessor. Check for EMC-correct connection of these cables. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 117: List Of Warnings And Alarms

    Feedback low (FEEDBACK < FDB LOW) Feedback high (FEEDBACK > FDB HIGH) Reference low (REF. < REF. LOW) Reference high (REF. > REF. HIGH) Temperature auto derate (TEMP.AUTO DERATE) Unknown fault (UNKNOWN ALARM) MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 118 1) VLT 4102-4402. The voltages stated are the intermediate circuit voltage of the VLT AFD with a tolerance of ± 5 %. The corresponding line voltage is the intermediate circuit voltage divided by √2. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 119 VLT AFD. The warning will only be enabled if parameter 804 Bus time interval function has been set to anything but OFF. If parameter 804 Bus time interval function has been set MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 120 AMA to be carried out. The setting in parameter Motor phase U between VLT AFD and motor is missing. 102 does not match the motor used. Turn off the VLT AFD and check motor phase U. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 121 The setting in parameter 102 Motor The remote reference is lower than parameter 225 power, P may not match the motor. Check the Warning: Low reference, REF motor and choose ‘Continue’ or [STOP]. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 122 (par. 411) is active. Warning: Temp. Auto derate. WARNING: 99 Unknown fault (UNKNOWN ALARM) An unknown fault has occurred which the software is not able to handle. Contact your Danfoss supplier. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 123: Special Conditions

    One indicator of aggressive airborn gasses is blackening fan. In very dusty environments, equipment with of copper rails and cable ends on existing installations. enclosure rating NEMA 12 or a cabinet for Chassis/ NEMA 1 equipment is recommended. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 124: Calculation Of Resulting Reference

    1. Power supply (SMPS) incl. signal isolation of U local/national regulations on PELV supplies. indicating the intermediate current voltage. In VLT 4000 VT all control terminals as well as 2. Gate drive that runs the IGTBs (trigger terminals 1-3 (AUX relay) are supplied from or in transformers/opto-couplers).
  • Page 125 - Suitable for power-up with short pulse-shaped during handling/operation of the AFD if (by mistake) charging current to ground the AFD has not been grounded. - Suitable for a high leakage current (300 mA) Leakage currents to ground MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 126: Extreme Running Conditions

    Switching on the output Switching on the output between the motor and the AFD is fully permitted. It is not possible to damage VLT 4000 VT in any way by switching on the output. However, fault messages may appear. Motor-generated overvoltage The voltage in the intermediate circuit is increased when the motor acts as a generator.
  • Page 127: Peak Voltage On Motor

    Rise time voltage 15 feet 575 V 0.38 µsec. 1430 V VLT 4102-4402 525-600 V Cable Line Peak length voltage Rise time voltage 75 feet 575 V 0.45 µsec. 1159 V MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 128 62 dB VLT 4016-4072 525-600 V IP20/NEMA 1 units: 66 dB VLT 4102-4402 525-600 V IP00/IP20/NEMA 1/NEMA 12 74 dB units: All units are measured 1 meter from the unit at full load. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 129: Derating For Ambient Temperature

    ® 4000 VT Derating for ambient temperature If VLT 4000 VT is operated at temperatures above 45 ºC, The ambient temperature (T ) is the maximum a derating of the continuous output current is necessary. AMB,MAX temperature allowed. The average (T AMB,MAX measured over 24 hours must be at least 5ºC lower.
  • Page 130 IEC 68-2-35: Random vibration broad-band in the electronics of the VLT AFD. - high reproducibility VLT 4000 VT has a pulse pattern in which it is possible IEC 68-2-36: Random vibration broad-band to set the switching frequency from 3.0- 10.0/14.0 kHz.
  • Page 131: Efficiency

    To calculate the system efficiency, the efficiency of frequency is set to a value of above 4 kHz (parameter VLT 4000 VT (VLT) is multiplied by the efficiency 407 Switching frequency). The rate of efficiency will of the motor (η...
  • Page 132 THD is calculated on the basis of the individual voltage harmonics using the following formula: < 0.1 11-49 To ensure low, harmonic currents, VLT 4000 VT has intermediate circuit coils as standard. This normally reduces the input current I by 40%.
  • Page 133: Definitions

    The control panel, which makes up a complete The difference between group 1 and group 2 is that interface for control and programming of VLT 4000 VT. in group 1 all stop signals must be cancelled for the The control panel is detachable and may, as an motor to start.
  • Page 134 There are four Setups, in which it is possible to save parameter settings. It is possible to change between the four parameter Setups and to edit one Setup, while another Setup is active. MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 135: Factory Settings

    0 - 100 % DC braking current 50 % 0 - 100 % DC braking time 0.0 - 60.0 sec. DC brake cut-in frequency 0.0-par. 202 Motor thermal protection ETR trip 1 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 136 This number refers to a conversion figure to be Integer 32 used when writing or reading to or from a VLT AFD Unsigned 8 by means of serial communication. Unsigned 16 Unsigned 32 Text string MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 137 This number refers to a conversion figure to be Integer 32 used when writing or reading to or from a VLT AFD Unsigned 8 Unsigned 16 by means of serial communication. Unsigned 32 Text string MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 138 424 PID start-up frequency 0.01 - 9999.00 s. (Off) 425 PID differentiation time 0.0 (Off) - 10.00 sec. 426 PID differentiator gain 5.0 - 50.0 limit 427 PID lowpass filter time 0.01 0.01 - 10.00 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 139 This number refers to a conversion figure to be Integer 32 used when writing or reading to or from a AFD Unsigned 8 by means of serial communication. Unsigned 16 Unsigned 32 Text string MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 140: Index

    ........................Efficiency Mechanical installation ..........Electrical installation, Motor thermal protection ..............Controlcables..............49 Motorcurrent ......................External 24 V DC supply Motorfrequency ............................. Externals: Motorpower ......................Extreme running conditions Motorvoltage MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 141 Safety regulations ............Service functions ..............Setpoint ................. Setup ............Setup configuration ......... Setup of user-defined readout ..........Shielded/armored cables ............. Single-pole start/stop ..............Sleep mode ............Status messages ............... Switches 1-4 MG.40.A7.22 - VLT is a registered Danfoss trademark...
  • Page 142 175R5443 MG40A722 *MG40A722* Rev. 2007-09-13...