8.2.33.15 Fault Code 49, ID 915 - Pre-charge
Cause
•
The DC-link voltage is too low to complete the synchronization.
Troubleshooting
•
Make sure that the synchronization threshold voltage is sufficient.
•
Make sure that the LC filter capacitance is not too large.
8.2.33.16 Fault Code 49, ID 916 - Pre-charge
Cause
•
AFE cannot synchronize with the grid voltage in the approved time limit.
Troubleshooting
•
Make sure that the grid voltage is stable or that the imbalance is not too high.
8.2.33.17 Fault Code 49, ID 917 - Pre-charge
Cause
•
Main contactor pilot relay close timeout.
•
The main contactor pilot relay did not close within the expected time.
Troubleshooting
•
Check the relay wiring.
8.2.33.18 Fault Code 49, ID 918 - Pre-charge
Cause
•
The AFE lost synchronization with the grid while it waited for the mains contactor to close.
Troubleshooting
•
–
8.2.33.19 Fault Code 49, ID 919 - Pre-charge
Cause
•
Main contactor close timeout.
•
The main contactor did not close within the expected time.
Troubleshooting
•
Check the main contactor wiring and main contactor pilot wiring.
8.2.33.20 Fault Code 49, ID 920 - Pre-charge
Cause
•
The main contactor opened during the DC stabilization phase.
Troubleshooting
•
Check the main contactor wiring and main contactor pilot wiring.
8.2.33.21 Fault Code 49, ID 921 - Pre-charge
Cause
•
The front end could not make the DC-link voltage stable in the necessary time.
•
The AFE was unable to commit to DC voltage control mode within the allotted time.
Troubleshooting
•
Make sure that the grid voltage feedback configuration is correct (line or phase voltage measurement).
•
Make sure that the feedback agrees with the AFE phase order.
•
Make sure that the phase shift of the potential transformer is accounted for in the PLL adaptation angle parameter.