VACON® 3000
Application Guide
INU application: P3.17.2.2.22
AFE application: P3.3.2.2.20
Use this parameter to select the digital input signal for interlock NC 1.
High = Active interlock for precharge and power from mains voltage.
7.420 (ID 3625) Interlock NC 2
Location in the menu:
INU application: P3.17.2.2.23
AFE application: P3.3.2.2.21
Use this parameter to select the digital input signal for interlock NC 2.
High = Active interlock for precharge and power from mains voltage.
7.421 (ID 3626) Interlock NC 3
Location in the menu:
INU application: P3.17.2.2.24
AFE application: P3.3.2.2.22
Use this parameter to select the digital input signal for interlock NC 3.
High = Active interlock for precharge and power from mains voltage.
7.422 (ID 3627) Interlock NC 4
Location in the menu:
INU application: P3.17.2.2.25
AFE application: P3.3.2.2.23
Use this parameter to select the digital input signal for interlock NC 4.
High = Active interlock for precharge and power from mains voltage.
7.423 (ID 3628) Interlock NO 1
Location in the menu:
INU application: P3.17.2.2.26
AFE application: P3.3.2.2.24
Use this parameter to select the digital input signal for interlock NO 1.
Low = Active interlock for precharge and power from mains voltage.
7.424 (ID 3629) Interlock NO 2
Location in the menu:
INU application: P3.17.2.2.27
AFE application: P3.3.2.2.25
Use this parameter to select the digital input signal for interlock NO 2.
Low = Active interlock for precharge and power from mains voltage.
7.425 (ID 3630) Interlock NO 3
Location in the menu:
INU application: P3.17.2.2.28
AFE application: P3.3.2.2.26
Use this parameter to select the digital input signal for interlock NO 3.
Low = Active interlock for precharge and power from mains voltage.
242 | Danfoss A/S © 2021.09
Parameter descriptions
AB319735759636en-000101 / DPD01822