Danfoss VACON 3000 Application Manual page 106

Table of Contents

Advertisement

VACON® 3000
Application Guide
Table 135: DC Voltage Control Parameters
Index
Parameter
P3.2.3.1
DC Voltage Reference
P3.2.3.2
DC Voltage Control Kp
P3.2.3.3
DC Voltage Control Ti
P3.2.3.4
Motoring Current Limit
P3.2.3.5
Regen Current Limit
Table 136: Line Filter Observer Parameters
Index
Parameter
P3.2.4.1
Active Damp Resistance
P3.2.4.5
Virtual LCCL Mix
Table 137: PLL Parameters
Index
Parameter
P3.2.5.1
Line PLL Gain
P3.2.5.2
Line PLL Integration Time
P3.2.5.3
PLL Minimum Frequency
P3.2.5.4
PLL Maximum Frequency
P3.2.5.5
Ref Frame Adapt Angle
Table 138: Reactive Power Control Parameters
Index
Parameter
P3.2.6.1
Reactive Current Reference
P3.2.6.2
Reactive Current Limit
P3.2.6.3
PFC Control Ki
Table 139: Modulation Parameters
Index
Parameter
P3.2.7.1
Switching Frequency
P3.2.7.2
Overmodulation
P3.2.7.3
Modulator Options
P3.2.7.4
Synchronous Modulation
106 | Danfoss A/S © 2021.09
Min
Max
105.00
120.00
1.00
800.00
0.0000
1.0000
0.0
150.0
0.0
150.0
Min
Max
0.000
100 000
0.000
100 000
Min
Max
0.00
800.00
0.0000
1.0000
0
320
45
320
-90.00
90.00
Min
Max
-75.00
75.00
0.0
70.0
0.00
800.00
Min
Max
Unit
Default
0.5
2.5
kHz
1.2
0
1
0
0
3
0
0
4
2
Unit
Default
ID
%
120.00
5001
%
300.00
5002
s
0.0060
5003
%
150.0
5005
%
150.0
5004
Unit
Default
ID
5 000
5054
%
41 000
5053
Unit
Default
ID
%
1.25
5060
s
0.5000
5061
Hz
45
5062
Hz
65
5063
-1.00
5064
Unit
Default
ID
%
0.00
5010
%
50.0
5012
%
25.00
5011
ID
Description
601
1515
0 = Disabled
1 = Enabled
3301
1 = Deadtime Compensation
2 = Startup Switching Frequency Reduce
3302
0 = Synchronous Modulation
1 = Asynchronous Modulation
2 = Symmetric Synchronous Modulation
AB319735759636en-000101 / DPD01822
AFE Application
Description
Description
Description
Description

Advertisement

Table of Contents
loading

Table of Contents