VACON® 3000
Application Guide
Use this parameter to select the response of the drive to a 'STO Fault'.
This parameter defines drive operation when Safe Torque Off (STO) function is activated (for example, emergency stop button has
been pressed or some other STO operation has been activated). See P3.9.1.2.
7.197 (ID 780) Overspeed Fault Response
Location in the menu:
INU application: P3.9.11.4
Use this parameter to select the response of the drive to the Over Speed Fault (fault ID 1084).
7.198 (ID 852) FB DataOut 1 Selection
Location in the menu:
INU application: P3.6.1
AFE application: P3.6.1
BCU application: P3.5.1
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
7.199 (ID 853) FB DataOut 2 Selection
Location in the menu:
INU application: P3.6.2
AFE application: P3.6.2
BCU application: P3.5.2
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
7.200 (ID 854) FB DataOut 3 Selection
Location in the menu:
INU application: P3.6.3
AFE application: P3.6.3
BCU application: P3.5.3
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
7.201 (ID 855) FB DataOut 4 Selection
Location in the menu:
INU application: P3.6.4
AFE application: P3.6.4
BCU application: P3.5.4
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
7.202 (ID 856) FB DataOut 5 Selection
Location in the menu:
INU application: P3.6.5
AFE application: P3.6.5
BCU application: P3.5.5
210 | Danfoss A/S © 2021.09
Parameter descriptions
AB319735759636en-000101 / DPD01822