Danfoss VACON 3000 Application Manual page 227

Table of Contents

Advertisement

VACON® 3000
Application Guide
Use this parameter to set the I gain for the torque controller in the sensorless control mode. The I Gain value 1.0 causes the integra-
tion to reach 1.0 Hz in 1 second when the torque error is 1% of the motor nominal torque.
This parameter is always active in sensorless torque control.
7.301 (ID 1736) Flux Trace Stabilator Gain
Location in the menu: P3.1.4.13.8
Use this parameter to set the gain of the flux trace stabilizer.
7.302 (ID 1737) Offset Voltage Alpha
Location in the menu: P3.1.5.8
Use this parameter to set a value for the offset voltage alpha in percent.
7.303 (ID 1738) Voltage Stabilator Gain
Location in the menu: P3.1.4.13.6
Use this parameter to set the gain of the voltage stabilizer.
7.304 (ID 1739) Offset Voltage Beta
Location in the menu: P3.1.5.9
Use this parameter to set a value for the offset voltage beta in percent.
7.305 (ID 1797) Flux Stabilator Gain
Location in the menu: P3.1.4.13.4
Use this parameter to set the gain of the flux stabilizer for induction motors.
7.306 (ID 1806) Password
Location in the menu:
INU application: P3.11.1
AFE application: P3.10.1
BCU application: P3.8.1
Use this parameter to set the administrator password.
7.307 (ID 1807) Fieldbus Watchdog Fault Mode
Location in the menu:
INU application: P3.9.1.10
AFE application: P3.8.1.19
BCU application: P3.6.1.8
Use this parameter to select the response of the drive to a 'Fieldbus Watchdog Fault'.
If Warning + Ramp up is used, the ramp speed can be set in the parameter.
7.308 (ID 1808) Fieldbus Watchdog Delay
Location in the menu:
INU application: P3.9.1.11
AFE application: P3.8.1.18
BCU application: P3.6.1.9
Use this parameter to set the delay for the response of the drive to a 'Fieldbus Watchdog Fault'.
The parameter defines the time how long the watchdog life bit has to be stopped before any action is made. If the parameter is set
to 0, the watchdog is disabled.
7.309 (ID 3001) Encoder Repeat Channel
Location in the menu: P3.15.2
Use this parameter to select which encoder channel to repeat:
Danfoss A/S © 2021.09
Parameter descriptions
AB319735759636en-000101 / DPD01822 | 227