VACON® 3000
Application Guide
7.169 (ID 720) Autoreset: Undervoltage
Location in the menu:
INU application: P3.10.6
AFE application: P3.9.6
BCU application: P3.7.6
Use this parameter to enable the automatic reset after an undervoltage fault.
7.170 (ID 721) Autoreset: Overvoltage
Location in the menu:
INU application: P3.10.7
AFE application: P3.9.7
BCU application: P3.7.7
Use this parameter to enable the automatic reset after an overvoltage fault.
7.171 (ID 722) Autoreset: Overcurrent
Location in the menu:
INU application: P3.10.8
AFE application: P3.9.8
BCU application: P3.7.8
Use this parameter to enable the automatic reset after an overcurrent fault.
7.172 (ID 723) Autoreset: AI Low
Location in the menu:
INU application: P3.10.9
AFE application: P3.9.9
BCU application: P3.7.9
Use this parameter to enable the automatic reset after a fault caused by low AI signal.
7.173 (ID 724) Autoreset: Unit Overtemperature
Location in the menu:
INU application: P3.10.10
AFE application: P3.9.10
BCU application: P3.7.10
Use this parameter to enable the automatic reset after a fault caused by unit overtemperature.
7.174 (ID 725) Autoreset: Motor Overtemperature
Location in the menu:
INU application: P3.10.11
AFE application: P3.9.11
Use this parameter to enable the automatic reset after a fault caused by motor overtemperature.
7.175 (ID 726) Autoreset: External Fault
Location in the menu:
INU application: P3.10.12
AFE application: P3.9.12
BCU application: P3.7.11
Use this parameter to enable the automatic reset after an external fault.
204 | Danfoss A/S © 2021.09