Danfoss VACON 3000 Application Manual page 47

Table of Contents

Advertisement

VACON® 3000
Application Guide
Table 24: Speed Control Settings
Index
Parameter
P3.1.2.4.1
CL Speed Control Kp
P3.1.2.4.2
CL Speed Control Ti
P3.1.2.4.3
Acceleration comp.TC
P3.1.2.4.4
Acceleration comp. filter TC
P3.1.2.4.5
Load Drooping Mode
P3.1.2.4.6
Load Drooping
P3.1.2.4.7
Load Drooping Time
P3.1.2.4.8
Speed error filter
Table 25: Limit Control Settings
Index
Parameter
P3.1.2.5.1
Overvoltage Control
P3.1.2.5.2
Undervoltage Control
P3.1.2.5.3
AFE In Use?
P3.1.2.5.4
OVC reference selection
P3.1.2.5.5
OVC reference
Table 26: Modulation Settings
Index
Parameter
P3.1.2.6.1
Switching Frequency
P3.1.2.6.2
Modulator Type
P3.1.2.6.3
Modulator Options
P3.1.2.6.4
Synchronous Modulation
Danfoss A/S © 2021.09
Min
Max
0.0
200.0
0.001
100 000
0.0000
100.0000
0.0000
10.0000
0
1
0.00
20.00
0.00
2.00
Min
Max
Unit
Default
0
1
1
0
1
1
0
1
0
0
V
0
Min
Max
Unit
Default
0.5
2.0
kHz
0.0
0
4
1
0
3
2
0
4
4
Unit
Default
ID
%
30.0
613
s
0.100
614
s
0.0000
626
s
0.0000
4001
0
1534
%
0.00
620
s
0.00
656
s
0.0000
4025
ID
Description
607
0 = Disabled
1 = Enabled
608
0 = Disabled
1 = Enabled
4003
0 = No
1 = Yes
4004
0 = Supply voltage
1 = DC voltage high maximum
2 = DC voltage high limit
4005
ID
Description
601
648
1 = SVM
2 = DPWM1
3 = DPWMIN
4 = No 3rd harmonic
3301
1 = Deadtime Compensation
2 = Switching Frequency Reduction At Start
3302
0 = Synchronous
1 = Asynchronous
4 = Soft Synchronous
AB319735759636en-000101 / DPD01822 | 47
INU Application
Description
0 = Normal
1 = Linear removal

Advertisement

Table of Contents
loading