ABB Relion 670 Series Technical Reference Manual page 554

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 8
Voltage protection
8.6.4
8.6.5
Table 282:
LOVPTUV (27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.1 - 9999.9
VPG
1 - 100
tTrip
0.000 - 60.000
Table 283:
LOVPTUV (27) Group settings (advanced)
Name
Values (Range)
tPulse
0.050 - 60.000
tBlock
0.000 - 60.000
tRestore
0.000 - 60.000
548
Input and output signals
Table 280:
LOVPTUV (27) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CBOPEN
BOOLEAN
VTSU
BOOLEAN
Table 281:
LOVPTUV (27) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Setting parameters
Unit
Step
-
-
kV
0.1
%VB
1
s
0.001
Unit
Step
s
0.001
s
0.001
s
0.001
Default
Description
-
Voltage connection
0
Block the all outputs
0
Circuit breaker open
0
Block from voltage circuit supervision
Description
Trip signal
Pickup signal
Default
Description
Disabled
Operation Enable/Disable
400.0
Base voltage
70
Pickup voltage in % of base voltage Vbase
7.000
Operate time delay
Default
Description
0.150
Duration of TRIP pulse
5.000
Time delay to block when all 3ph voltages are
not low
3.000
Time delay for enable the function after
restoration
1MRK505222-UUS C
Technical reference manual