ABB Relion 670 Series Technical Reference Manual page 495

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
7.13.5
Table 249:
BRCPTOC (46) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
0 - 99999
Pickup_ub
50 - 90
Pickup_PH
5 - 100
tOper
0.000 - 60.000
Table 250:
BRCPTOC (46) Group settings (advanced)
Name
Values (Range)
tReset
0.010 - 60.000
7.13.6
Technical reference manual
Table 248:
BRCPTOC (46) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
%IM
1
%IB
1
s
0.001
Unit
Step
s
0.001
Technical data
Table 251:
BRCPTOC (46) technical data
Function
Minimum phase current for operation
Unbalance current operation
Timer
Description
Operate signal of the protection logic
Pickup signal of the protection logic
Default
Description
Disabled
Operation Disable / Enable
3000
IBase
50
Unbalance current operation value in percent
of max current
20
Minimum phase current for operation of
pickup_ub> in % of Ibase
5.000
Operate time delay
Default
Description
0.100
Time delay in reset
Range or value
IBase
(5–100)% of
(0–100)% of maximum current
(0.00-6000.00) s
Section 7
Current protection
Accuracy
± 0.1% of I
n
± 0.1% of I
n
± 0.5% ± 10 ms
489