ABB Relion 670 Series Technical Reference Manual page 456

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
7.7.2
450
The three-phase current measuring protection has an I
time constant and a thermal memory..
An alarm pickup gives early warning to allow operators to take action well before the
line is tripped.
Principle of operation
The sampled analog phase currents are pre-processed and for each phase current the
RMS value is derived. These phase current values are fed to the thermal overload
protection, one time constant function LPTTR. (26).
From the largest of the three-phase currents a final temperature is calculated according
to the expression:
2
æ
ö
I
Q
=
×
ç
÷
T
ç
÷
final
ref
I
è
ø
ref
EQUATION1167 V1 EN
where:
I
is the largest phase current,
I
is a given reference current and
ref
T
is steady state temperature rise corresponding to I
ref
The ambient temperature is added to the calculated final temperature. If this
temperature is larger than the set operate temperature level, TripTemp, a PICKUP
output signal is activated.
The actual temperature at the actual execution cycle is calculated as:
1MRK505222-UUS C
2
t characteristic with settable
ref
Technical reference manual
(Equation 92)