ABB Relion 670 Series Technical Reference Manual page 354

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
348
D
Rv
LdAngle
D
D
Rv
j
ANSI05000175 V2 EN
Figure 184:
Operating characteristic for ZMRPSB (68) function (setting parameters
in italic)
The impedance measurement within ZMRPSB (68) function is performed by solving
equation
72
and equation
applicable for phases B and C).
æ
ö
V
A
£
Re
Rset
ç
÷
I
è
ø
A
EQUATION1557 V1 EN
æ
ö
V
A
£
Im
Xset
ç
÷
I
è
ø
A
EQUATION1558 V1 EN
The R
and X
are R and X boundaries.
set
set
jX
X1OutFw
X1InFw
R1FInRv
D
Rv
Rv
RLdInRv
RLdInFw
RLdOutRv
D
Rv
73
(Typical equations are for phase A, similar equations are
1MRK505222-UUS C
R1LIn
ZL
D
Fw
R1FInFw
j
D
Fw
D
Fw
D
Fw
D
Fw
RLdOutFw
X1InRv
X1OutRv
ANSI05000175-2-en.vsd
Technical reference manual
j
D
Fw
LdAngle
R
(Equation 72)
(Equation 73)