ABB Relion 670 Series Technical Reference Manual page 992

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Metering
16.1.3
16.1.4
986
The BLOCK input is set, or
The Binary Input Module, where the counter input is situated, is inoperative.
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
Note, the pulse is short, one cycle.
The SCAL_VAL signal consists of scaled value (according to parameter Scale), time
and status information.
Function block
PCGGIO
BLOCK
INVALID
READ_VAL
RESTART
BI_PULSE*
BLOCKED
RS_CNT
NEW_VAL
SCAL_VAL
IEC05000709-2-en.vsd
IEC05000709 V3 EN
Figure 482:
PCGGIO function block
Input and output signals
Table 603:
PCGGIO Input signals
Name
Type
BLOCK
BOOLEAN
READ_VAL
BOOLEAN
BI_PULSE
BOOLEAN
RS_CNT
BOOLEAN
Table 604:
PCGGIO Output signals
Name
Type
INVALID
BOOLEAN
RESTART
BOOLEAN
BLOCKED
BOOLEAN
NEW_VAL
BOOLEAN
SCAL_VAL
REAL
Default
Description
0
Block of function
0
Initiates an additional pulse counter reading
0
Connect binary input channel for metering
0
Resets pulse counter value
Description
The pulse counter value is invalid
The reported value does not comprise a complete
integration cycle
The pulse counter function is blocked
A new pulse counter value is generated
Scaled value with time and status information
1MRK505222-UUS C
Technical reference manual