Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
6.9.5
Table 152:
ZMRPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
X1PP
0.10 - 3000.00
R1PP
0.01 - 1000.00
RFPP
0.10 - 3000.00
X1PG
0.10 - 3000.00
R1PG
0.01 - 1000.00
X0PG
0.10 - 9000.00
R0PG
0.01 - 3000.00
RFPG
0.10 - 9000.00
OperationPP
Disabled
Enabled
Timer tPP
Disabled
Enabled
tPP
0.000 - 60.000
OperationPG
Disabled
Enabled
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
IMinOpIR
5 - 1000
Technical reference manual
Table 151:
ZDRDIR (21D) Output signals
Name
Type
STDIRCND
INTEGER

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
-
-
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
-
-
-
-
s
0.001
-
-
-
-
s
0.001
%IB
1
%IB
1
%IB
1
Description
Binary coded directional information per measuring loop
Default
Description
Enabled
Operation Disable / Enable
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
30.00
Positive sequence reactance reach Ph-Ph
5.00
Positive seq. resistance for characteristic
angle, Ph-Ph
30.00
Fault resistance reach in ohm/loop, Ph-Ph
30.00
Positive sequence reactance reach Ph-G
5.00
Positive seq. resistance for characteristic
angle, Ph-G
100.00
Zero sequence reactance reach, Ph-G
15.00
Zero seq. resistance for zone characteristic
angle, Ph-G
100.00
Fault resistance reach in ohm/loop, Ph-G
Enabled
Operation mode Disable/Enable of Phase-
Phase loops
Enabled
Operation mode Disable/Enable of Zone
timer, Ph-Ph
0.000
Time delay of trip, Ph-Ph
Enabled
Operation mode Disable/Enable of Phase-
Ground loops
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
0.000
Time delay of trip, Ph-G
20
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
20
Minimum pickup phase current for Phase-to-
ground loops
5
Minimum operate residual current for Phase-
Ground loops
Section 6
Impedance protection
323