Principle of operation

Full scheme measurement

The execution of the different fault loops within the IED are of full scheme type, which
means that each fault loop for phase-to-ground faults and phase-to-phase faults are
executed in parallel.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a phase selector element to select correct voltages and
current depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.

Impedance characteristic

The distance function consists of five instances. Each instance can be selected to be
either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The operating
characteristic is in accordance to figure
Mho, zone4
Mho, zone3
Mho, zone2
Mho, zone1
R
Offset mho, zone5
Impedance protection
117
where zone 5 is selected offset mho.
X
Section 6
Zs=0
R
Zs=Z1
Zs=2Z1
IEC09000143_2_en.vsd