Section 7
Current protection
7.4.2
7.4.2.1
400
Directional operation can be combined together with corresponding communication
logic in permissive or blocking teleprotection scheme. Current reversal and weak-end
infeed functionality are available as well.
EF4PTOC (51N/67N) can be configured to measure the residual current from the three-
phase current inputs or the current from a separate current input.
Principle of operation
This function has the following three "Analog Inputs" on its function block in the
configuration tool:
1.
I3P, input used for "Operating Quantity".
2.
V3P, input used for "Voltage Polarizing Quantity".
3.
I3PPOL, input used for "Current Polarizing Quantity".
These inputs are connected from the corresponding pre-processing function blocks in
the Configuration Tool within PCM600.
Operating quantity within the function
The function always uses Residual Current (3I
current can be:
1.
directly measured (when a dedicated CT input of the IED is connected in PCM600
to the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input I3P). This dedicated IED CT input can be for example,
connected to:
parallel connection of current instrument transformers in all three phases
(Holm-Green connection).
one single core balance, current instrument transformer (cable CT).
one single current instrument transformer located between power system
WYE point and ground (that is, current transformer located in the neutral
grounding of a WYE connected transformer winding).
one single current instrument transformer located between two parts of a
protected object (that is, current transformer located between two WYE
points of double WYE shunt capacitor bank).
2.
calculated from three-phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
Analog Input I3P is not connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I
three inputs into the pre-processing block by using the following formula (will
1MRK505222-UUS C
) for its operating quantity. The residual
0
0
Technical reference manual
from the first