Figure 14:
Activation of new disturbance
In order not to have a lock-up of the indications in the case of a persisting signal each
LED is provided with a timer, tMax, after which time the influence on the definition of
a disturbance of that specific LED is inhibited. This functionality is shown i diagram in
figure 15.
Activating signal
ANSI05000507 V1 EN
Figure 15:
Length control of activating signals
Timing diagram for sequence 6
Figure 16
shows the timing diagram for two indications within one disturbance.
OR
tRestart
0
AND
0-100s
AND
OR
To LED
To disturbance
AND
length control
0-tMax
0
en05000507_ansi.vsd
Section 3
Local HMI
New
disturbance
OR
AND
en01000237_ansi.vsd
67