Minimum operating current
The operation of Distance measuring zones, quadrilateral characteristic (ZMRPDIS,
21) is blocked if the magnitude of input currents fall below certain threshold values.
The phase-to-ground loop AG (BG or CG) is blocked if IA (IB or IC) < IMinPUPG.
For zone 1 with load compensation feature the additional criterion applies, that all phase-
to-ground loops can be blocked when IN < IMinOpIR, regardless of the phase currents.
IA (IB or IC) is the RMS value of the current in phase IA (IB or IC). IN is the RMS
value of the vector sum of the three-phase currents, that is residual current 3I
The phase-to-phase loop AB (BC or CA) is blocked if I
All three current limits IMinPUPG, IMinOpIR and IMinPUPP are
automatically reduced to 75% of regular set values if the zone is set to
operate in reverse direction, that is OperationDir=Reverse
Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the