1MRK505222-UUS C
6.10.5
Table 158:
FRPSPDIS (21) Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
3I0BLK_PP
10 - 100
3I0Enable_PG
10 - 100
RLdFwd
1.00 - 3000.00
RldRev
1.00 - 3000.00
LdAngle
5 - 70
X1
0.50 - 3000.00
R1PP
0.10 - 1000.00
X1FwPG
0.10 - 1000.00
X0
0.50 - 9000.00
Table continues on next page
Technical reference manual
Name
Type
REV_B
BOOLEAN
REV_C
BOOLEAN
REV_G
BOOLEAN
NDIR_A
BOOLEAN
NDIR_B
BOOLEAN
NDIR_C
BOOLEAN
NDIR_G
BOOLEAN
FWD_1PH
BOOLEAN
FWD_2PH
BOOLEAN
FWD_3PH
BOOLEAN
PHG_FLT
BOOLEAN
PHPH_FLT
BOOLEAN
PHSELZ
INTEGER
DLECND
INTEGER

Setting parameters

Unit
Step
A
1
kV
0.01
%IPh
1
%IPh
1
ohm/p
0.01
ohm/p
0.01
Deg
1
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
Description
Fault detected in phase B - reverse direction
Fault detected in phase C - reverse direction
Ground fault detected in reverse direction
Non directional fault detected in Phase A
Non directional fault detected in Phase B
Non directional fault detected in Phase C
Non directional phase-to-ground fault detected
Single phase-to-ground fault in forward direction
Phase-to-phase fault in forward direction
Three phase fault in forward direction
Release condition to enable phase-ground measuring
elements
Release condition to enable phase-phase measuring
elements
21 pickup with load encroachment and 3I0
Pickup for load encroachment and 3I0
Default
Description
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
40
3I0 limit for disabling phase-to-phase
measuring loops
20
3I0 pickup for releasing phase-to-ground
measuring loops
80.00
Forward resistive reach for the load
impedance area
80.00
Reverse resistive reach for the load
impedance area
30
Load angle determining the load impedance
area
40.00
Positive sequence reactance reach
15.00
Positive seq. resistance for characteristic
angle, Ph-Ph
1.50
Positive seq. resistance for characteristic
angle, Ph-G
120.00
Zero sequence reactance reach
Section 6
Impedance protection
345