ABB Relion 670 Series Technical Reference Manual page 681

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
12.3.7.5
Table 340:
SXCBR Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SuppressMidPos
Disabled
Enabled
12.3.8
12.3.8.1
Technical reference manual
Name
Type
SUBSTED
BOOLEAN
OP_BLKD
BOOLEAN
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
TR_POS
INTEGER
CNT_VAL
INTEGER
L_CAUSE
INTEGER
Setting parameters
Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
Circuit switch SXSWI
Introduction
The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or grounding switches via binary
output boards and to supervise the switching operation and position.
Description
Indication that the position is substituted
Indication that the function is blocked for open
commands
Indication that the function is blocked for close
commands
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Truck position indication
Operation counter value
Latest value of the error indication during command
Default
Description
0.100
Supervision time for the apparatus to move
after a command
0.150
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end
position is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Enabled
Mid-position is suppressed during the time
tIntermediate
Section 12
Control
675