Section 8
Voltage protection
8.3.4
8.3.5
Table 266:
ROV2PTOV (59N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.05 - 2000.00
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Pickup1
1 - 200
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
Table continues on next page
526
Input and output signals
Table 264:
ROV2PTOV (59N) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR1
BOOLEAN
BLK1
BOOLEAN
BLKTR2
BOOLEAN
BLK2
BOOLEAN
Table 265:
ROV2PTOV (59N) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
Setting parameters
Unit
Step
-
-
kV
0.05
-
-
-
-
%VB
1
s
0.01
s
0.001
Default
Description
-
Three phase voltages
0
Block of function
0
Block of trip signal, step 1
0
Block of step 1
0
Block of trip signal, step 2
0
Block of step 2
Description
Trip
Common trip signal from step1
Common trip signal from step2
General pickup signal
Common pickup signal from step1
Common pickup signal from step2
Default
Description
Disabled
Disable/Enable Operation
400.00
Base voltage
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step 1
30
Voltage setting/pickup value (DT & TOV),
step 1 in % of VBase
5.00
Definitive time delay of step 1
5.000
Minimum operate time for inverse curves for
step 1
1MRK505222-UUS C
Technical reference manual