Section 12
Control
Table 395:
DNPGEN Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Table 396:
CHSERRS485 Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Serial-Mode
BaudRate
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
WireMode
Four-wire
Two-wire
Table 397:
CHSERRS485 Non group settings (advanced)
Name
Values (Range)
DLinkConfirm
Never
Sometimes
Always
tDLinkTimeout
0.000 - 60.000
DLinkRetries
0 - 255
tRxToTxMinDel
0.000 - 60.000
ApLayMaxRxSize
20 - 2048
ApLayMaxTxSize
20 - 2048
StopBits
1 - 2
Parity
No
Even
Odd
tRTSWarmUp
0.000 - 60.000
tRTSWarmDown
0.000 - 60.000
tBackOffDelay
0.000 - 60.000
tMaxRndDelBkOf
0.000 - 60.000
770
Unit
Step
Default
-
-
Disabled
Unit
Step
Default
-
-
Disabled
-
-
9600 Bd
-
-
Two-wire
Unit
Step
Default
-
-
Never
s
0.001
2.000
-
1
3
s
0.001
0.000
-
1
2048
-
1
2048
-
1
1
-
-
Even
s
0.001
0.000
s
0.001
0.000
s
0.001
0.050
s
0.001
0.100
1MRK505222-UUS C
Description
Disable/Enable Operation
Description
Operation mode
Baud-rate for serial port
RS485 wire mode
Description
Data-link confirm
Data-link confirm timeout in s
Data-link maximum retries
Rx to Tx minimum delay in s
Application layer maximum Rx fragment size
Application layer maximum Tx fragment size
Stop bits
Parity
RTS warm-up in s
RTS warm-down in s
RS485 back-off delay in s
RS485 maximum back-off random delay in s
Technical reference manual