Section 4
Basic IED functions
Table 50:
SMAI2 Non group settings (basic)
Name
Values (Range)
DFTReference
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
TYPE
1 - 2
Table 51:
SMAI2 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
VBase
0.05 - 2000.00
4.13
4.13.1
4.13.2
114
Unit
Step
-
-
-
-
Ch
1
Unit
Step
-
-
%
1
kV
0.05

Summation block 3 phase 3PHSUM

Introduction

Summation block 3 phase function 3PHSUM is used to get the sum of two sets of three-
phase analog signals (of the same type) for those IED functions that might need it.

Principle of operation

Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
Default
Description
InternalDFTRef
DFT reference
Ph-N
Input connection type
1
1=Voltage, 2=Current
Default
Description
Disabled
Negation
10
Limit for frequency calculation in % of VBase
400.00
Base voltage
1MRK505222-UUS C
Technical reference manual