ABB Relion 670 Series Technical Reference Manual page 687

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
12.3.8.5
Table 343:
SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
SuppressMidPos
Disabled
Enabled
12.3.9
12.3.9.1
Technical reference manual
Name
Type
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
CNT_VAL
INTEGER
L_CAUSE
INTEGER
Setting parameters
Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
-
-
Bay reserve QCRSV
Introduction
The purpose of the reservation function is primarily to transfer interlocking
information between IEDs in a safe way and to prevent double operation in a bay,
switchyard part, or complete substation.
Description
Indication that the function is blocked for close
commands
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Operation counter value
Latest value of the error indication during command
Default
Description
3.000
Supervision time for the apparatus to move
after a command
15.000
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end
position is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Disconnector
1=LoadBreak,2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
Enabled
Mid-position is suppressed during the time
tIntermediate
Section 12
Control
681