The blocking facilities provided by the bay control function are the following:
Blocking of position indications, BL_UPD. This input will block all inputs related
to apparatus positions for all configured functions within the bay.
Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC 61850–
8–1). If DO Behavior is set to "blocked" it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional
and configuration data is visible.
The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been
defined in the IED. Otherwise the default authority level, SuperUser, can handle the
control without LogOn. The users and passwords are defined in PCM600.
Function block
QCBAY
LR_OFF
PSTO
LR_LOC
UPD_BLKD
LR_REM
CMD_BLKD
LR_VALID
LOC
BL_UPD
REM
BL_CMD
IEC10000048-1-en.vsd
IEC10000048 V1 EN
Figure 327:
QCBAY function block
Input and output signals
Table 327:
QCBAY Input signals
Name
Type
LR_OFF
BOOLEAN
LR_LOC
BOOLEAN
LR_REM
BOOLEAN
LR_VALID
BOOLEAN
BL_UPD
BOOLEAN
BL_CMD
BOOLEAN
Default
Description
0
External Local/Remote switch is in Off position
0
External Local/Remote switch is in Local position
0
External Local/Remote switch is in Remote position
0
Data representing the L/R switch position is valid
0
Steady signal to block the position updates
0
Steady signal to block the command
Section 12
Control