ABB Relion 670 Series Technical Reference Manual page 555

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
8.6.6
Technical reference manual
Technical data
Table 284:
LOVPTUV (27) technical data
Function
Operate voltage
Pulse timer
Timers
Range or value
(0–100)% of VBase
(0.050–60.000) s
(0.000–60.000) s
Section 8
Voltage protection
Accuracy
± 0.5% of V
n
± 0.5% ± 10 ms
± 0.5% ± 10 ms
549