ABB Relion 670 Series Technical Reference Manual page 884

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Logic
Table 518:
SRMEMORY Group settings (basic)
Name
Values (Range)
Memory
Disabled
Enabled
14.3.10
878
Table 517:
SRMEMORY Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Unit
Step
-
-
Reset-set with memory function block RSMEMORY
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory
that can reset or set an output from two inputs respectively. Each RSMEMORY
function block has two outputs, where one is inverted. The memory setting controls if
the flip-flop after a power interruption will return the state it had before or if it will be
reset. For a Reset-Set flip-flop, RESET input has higher priority over SET input.
Table 519:
Truth table for RSMEMORY function block
RESET
SET
OUT
0
0
0
1
1
0
1
1
RSMEMORY
SET
OUT
RESET
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 444:
RSMEMORY function block
Table 520:
RSMEMORY Input signals
Name
Type
SET
BOOLEAN
RESET
BOOLEAN
Description
Output signal
Inverted output signal
Default
Enabled
NOUT
Last
Inverted last
value
value
1
0
0
1
0
1
Default
Description
0
Input signal to set
0
Input signal to reset
1MRK505222-UUS C
Description
Operating mode of the memory function
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670