Section 7
Current protection
7.10.5
Table 231:
CCRPLD (52PD) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
tTrip
0.000 - 60.000
ContactSel
Disabled
PD signal from CB
Pole pos aux cont.
CurrentSel
Disabled
CB oper monitor
Continuous monitor
CurrUnsymPU
0 - 100
CurrRelPU
0 - 100
7.10.6
7.11
470
Table 230:
CCRPLD (52PD) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Setting parameters
Unit
Step
-
-
-
1
s
0.001
-
-
-
-
%
1
%IB
1
Technical data
Table 232:
CCRPLD (52PD) technical data
Function
Operate current
Time delay
Directional underpower protection GUPPDUP (37)
Function description
Directional underpower protection
Description
Trip signal to CB
Trip condition TRUE, waiting for time delay
Default
Description
Disabled
Disable/Enable Operation
3000
Base current
0.300
Time delay between trip condition and trip
signal
Disabled
Contact function selection
Disabled
Current function selection
80
Unsym magn of lowest phase current
compared to the highest.
10
Current magnitude for release of the function
in % of IBase
Range or value
IBase
(0–100)% of
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
GUPPDUP
1MRK505222-UUS C
Accuracy
± 1.0% of I
n
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
37
P <
SYMBOL-LL V1 EN